8.2.2 MODES AND PARAMETERS TO BE ESTABLISHED ON THE KL1 CONTROL UNIT

The control unit features four programming keys:
key to confirm the modified data.
ENTER
key to select the figure to be modified.
SHIFT
key to increase the number to be modified or go to the upper parameter line.
INCREASE
DECREASE
To access the programming mode proceed as follows:
Turn the SA4 selector switch to * (the system stops).
The display shows the main page.
Strike the
Strike the
strike the
Strike the
Enter the number 20009 then strike
while the number 20009 will appear in the bottom string.
Strike the
Strike the
DECREASE
N. of pumps
running
% inverter
pumps speed
Number pump fed from
inverter

8.2.3 PAGE PARAMETER TABLE, ALWAYS DISPLAYED IN THE KL1 CONTROL UNIT

PSET 00,0 P 00,0
NP0 Vel%00 INV
Q.:
0(L/M)
QT:
000(L)
KW:
0.0
kWh:
0.0
P1h: 00000
P2h: 00000
P3h: 00000
P4h: 00000
Software vers.
EBARA 16.003.001.2 c21
(*) = optional units.
key to decrease the number to be modified or go to the lower parameter line.
key until you reach the bottom parameter line, the following message will appear: "enter key".
DECREASE
key; the 0 on the right will start flashing; modify the parameter using the
SHIFT
key, the 0 to the left of the number you have just modified will start flashing.
SHIFT
key until you reach the fifth figure, then modify with number 1 using the
SHIFT
ENTER
key, the message: Language 1: ENGLISH will appear on the display.
DECREASE
key to view and modify the parameters dedicated to SERVICE EBARA (see table
Set
Instantaneous
pressure
pressure
P.Set00.0
NP0 Vel%00 INV:0
Main page displays:
PSET= Pressure setting.
P= instantaneous system pressure.
NP0= Number of pumps running.
Vel%= Speed % of pump powered by the inverter.
INV= number of pump supply with inverter.
Q= instantaneous flow (*)
QT= flow totalization. (*)
KW= instantaneous pumpset power consumption. (*)
KWh= Totalization of pumpset power consumption. (*)
P1h =pump 1 operating hours
P2h =pump 2 operating hours
P3h =pump 3 operating hours
P4h =pump 4 operating hours
Software personalized for EBARA.
ENGLISH
key:
appears the message "Serv. access key" will appear in the top string,
Increase
button
P00.0
INCREASE
SHIFT
ENTER
DECREASE
26
key until you reach 9, then
INCREASE
key.
INCREASE
8.2.5).
Confirm button
Decrease button
Shift button