Tools Required: (2) 7/16" socket or box wrenches.
To position the handle at operating height:
Step 1: Remove and keep the hardware securing the
handle to the legs.
Step 2: Raise handle until holes align with the upper
holes in the legs.
Step 3: Re-insert hardware as shown,
securely.
THE PROPER SIZE SO- type feeder cable MUST BE USED for the electrical hook-up of this heater. The proper cable size is shown
in the tables below (A.W.G./ # of conductors.) Table 1 is for cable 50ft. in length or less. Table 2 is for cable longer than 50ft.
A 25ft. cable kit can be purchased from the
factory. Refer to the kit part numbers in table at
right.
CABLE KITS INCLUDE:
25 feet of Type SO cable, with either 3-
•
conductors or 4-conductors, depending on
the heater requirements.
To order cable kits
Phone: 1-800-495-4525
Feeder cable or cable kit assembly MUST BE made by
•
licensed electricians ONLY.
Service panel or receptacle used to supply power to
•
these heaters MUST have a ground bus or ground pole
that is securely bonded to earth ground.
Connect green ground conductor on feeder cable or
•
cable kit to grounding lug on heaters.
Comply with ALL local electrical codes and the
•
National Electric Code (NFPA70) when providing
electrical power to these heaters.
Issue Date: 4-19-02 Rev. Date: 12-21-05 Rev. Level: 12
FES – SERIES ASSEMBLY
and fasten
WIRING
Model
Table 1
FES & YES 1520-3A
FES & YES 1524-1A
FES & YES 1524-3E
FES & YES 1548-3E
FES & YES 1560-3A
FES & YES 3048-3A
FES & YES 3060-3A
Model
Table 2
FES & YES 1520-3A
FES & YES 1524-1A
FES & YES 1524-3E
FES & YES 1548-3E
FES & YES 1560-3A
FES & YES 3048-3A
FES & YES 3060-3A
Bolts
Washers
Washers
Unit Rating
Cable Size - Under
15kW, 208 Volt, 3-Ph
15kW, 240 Volt, 1-Ph
15kW, 240 Volt, 3-Ph
15kW, 480 Volt, 3-Ph
15kW, 600 Volt, 3-Ph
30kW, 480 Volt, 3-Ph
30kW, 600 Volt, 3-Ph
Unit Rating
15kW, 208 Volt, 3-Ph
15kW, 240 Volt, 1-Ph
15kW, 240 Volt, 3-Ph
15kW, 480 Volt, 3-Ph
15kW, 600 Volt, 3-Ph
30kW, 480 Volt, 3-Ph
30kW, 600 Volt, 3-Ph
ELECTRICAL SHOCK
FIRE HAZARD
Serious injury or death may
•
occur.
Disconnect from electrical
•
supply before installing feeder
cable to these heaters.
Read and follow all safety
•
information in box to the left.
OIPM P/N 3420458
Nuts
Cable
50ft. long
Kit Number
6/4
03164001
4/3
08805300
6/4
03164001
12/4
03164201
12/4
03164201
6/4
03164001
6/4
03164001
Cable Size – Over
Max. Cable
50ft. long
Length (ft)
4/4
120
2/3
215
6/4
150
12/4
140
12/4
190
6/4
300
6/4
350