All wires must be firmly connected.
Make sure all the wire not touching the refrigerant piping, compressor or any moving parts of the fan motor.
The connecting wire between the indoor unit and the outdoor unit must be clamped on the wire clamps.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
When attaching the terminal box lid, make sure do not pinch any wires.
After all the wiring connections are done, fill in any gaps/holes with insulation (procured locally) to prevent small animals
and insects entering the unit from outside.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Step to connect the installation wire:
Used the correct screwdriver for tightening the terminal screws. If the block is too small, the mad of the screw might be
damaged and the screw will not be properly tightened. If tightening too hard, screw might be damaged.
Do not connect wire at different gauge to the same proper supply terminal.
Use specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying excessive
force to the terminal.
Keep wiring in mat order and not to obstruct other equipment such as popping open the terminal box lid.
Connect wires of the
same gauge to both side.

Operating Limits:

Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes), 35°C ~ 70°C (4 Pipes),
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Unit
Temperature
Ts °C/°F
Minimum indoor
16.0 / 60.8
temperature
Maximum indoor
32.0 / 89.6
temperature
Attach insulation sleeve
Round crimp-style terminal
Do not connect wires of the
same gauge to one side.

OPERATING RANGE

Heating Unit
Th °C/°F
Temperature
Minimum indoor
11.0 / 51.8
temperature
Maximum indoor
23.0 / 73.4
temperature
Ts: Dry bulb temperature.
1-10
Electric wire
Do not connect wires
of different gauges.
Ts °C/°F
16.0 / 60.8
30.0 / 86.0
Th: Wet bulb temperature.