IN THIS CONFIGURATION, THE BOILER
SATISFIES 4 HEATING AREAS THROUGH
FOUR AREA VALVES WITH MICRO LIMIT
SWITCH AND CIRCULATOR.
- Connect the room thermostats to the
system expansion board inputs and power
the corresponding area valves via the relative
outputs.
- Interrupt the circulator electric power supply
via the area valves micro limit switches.
- Connect clamp OC+- of the system expansion
board to the boiler via AUX clamp. Pay attention
to the polarity of the cables! (red = +, black = -).
- Power the system expansion board (F-N).
- Use the boiler display to set parameter
PH13=1 (active Z4)
NOTE: SINCE VERSION V6 Z4, IT IS ALREADY
ENABLED BY FACTORY
With all thermostats satis ed (contacts open),
the boiler switches o .
THE LAYOUTS GIVEN IN THIS MANUAL ARE INDICATIVE AND NOT COMPLETE OF ALL COMPULSORY SAFETY DEVICES ENVISIONED BY LAWS AND STANDARDS IN FORCE.