Requirement of installation
Please observe the following requirement. Otherwise, it may cause the product
aging and breakdown.
The applicable ambient temperature
of this product is in the range of
-10°C ~ 40°C.
Do not install the product where it is
exposed to oil fumes.
The lowest surface of this product
should be installed above 2.3m from
the floor after installation.
Avoiding any accident.
Please install the product horizontally,
don't vertically install the product.
It could affect the
performance of bearing.
5
2.3m above
It's prohibited to install in the uneven
surface. (Flatness shall be 3mm below.)
Distortion results in reducing the
separation performance.
Locations where freezing could happen.
Otherwise, it may damage the
product or cause fire.
Do not install the product in the place
with many dust.
Impeller deformation may be
caused by sand and dust piling
up, which may affect the
performance.
The distance between product and
ceiling must be 50mm above.
The ceiling is excessively
close to air inlet that may
reduce the separation
performance.
Ensure the space among products is
20 ~ 40mm when multiple products
operate in row.
Easy for installation.
Please block the clearance between
wall and product.
50mm above
20 ~ 40mm
Prevent product
from sucking in
outdoor air from
clearances.