The receiver microprocessor reads the position of the jumpers JP1-4 at start-up: if there
has been a variation in the configuration of the jumpers JP1-4, to implement these
changes, you must turn the receiver OFF and back ON again.
Pulse functioning. JP1 and JP2 open: for every
button enabling
transmitter command given, the output is enabled for
1 s
output
a second.
Step functioning. JP1 closed: for every transmitter
button enabling
command given, the output changes state
output
(ON ð OFF and OFF ð ON).
Continuous functioning. JP2 closed: the output
button enabling
remains active as long as the transmitter command
output
persists.
CONFIGURATION NOT USED AS IT DISABLES THE OUTPUT
CHANNELS 3 AND 4.

4. CHECKING THE OPERATION

After selecting the operating mode and times, check the external devices connected to
the card and check the state of the LED's.
4.1 CHECKING THE OPERATION OF EXTERNAL DEVICES
Start input - N.O. type contact which supplies the start pulse to the automation.
Stop input - N.C. safety contact which has priority in all states and functions. If the stop
input is given, the device blocks the gate immediately and it only starts up again when the
start pushbutton is pressed: this closes the automation. When the stop input is given, the
device ignores all the commands.
Photocell input - N.C. safety contact which is only enabled during closing. If the
photocell is obscured, the automation stops for 1 second and the gate then re-opens as
far as the limit switch. When the gate is open and the photocells are obscured, the
photocells block gate closing.
Opening/closing safety device input - The function of this input connected to terminal
6 depends on the operating mode. The following is a list of the possible functions.
Opening safety device input - N.C. contact enabled in automatic and in the two alternatives
of the semiautomatic mode. This is a safety device input which is enabled during closing
and opening. When the input is enabled, the gate is stopped immediately. When the input
is disabled, the gate starts to move in the same direction as before after a delay of 1
second. This function can be used to protect the areas where crushing may occur.
Closing input - Input which is only enabled when Dead Man mode is selected. It closes the
automation when the close pushbutton is pressed and held down (terminal 6).
Warning light output - 24VDC output with maximum load of 3W, which commands the
gate state warning light. Light OFF: gate closed. Steady light: gate open or opening.
Flashing light: gate closing.
Flashing light output - 24 V output which commands the flashing light.
This output commands the flashing light with a pulsating power supply with frequency of 1
Hz: the light comes ON for 0.5 seconds and OFF for 0.5 sec. If pre-flashing is enabled, this
output is enabled 3 seconds before the command to move the gate (opening and closing).
NOTE - Only use Aprimatic ET Series LED flashing lights or the output may break down:
this will cause the entire system to malfunction.