Set Maintenance Period - Theben RAMSES 850 top2 OT Instrucciones De Montaje Y De Uso

Ocultar thumbs Ver también para RAMSES 850 top2 OT:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 110
Set room influence
With weather-dependent control, the feed
temperature can be adjusted if there is a large
divergence between the room temperature and
the setpoint temperature.
Offset supply temperature
Set room influence
Setpoint value of room temperature = T
Actual value of room temperature
∆ Tv
= PI (T
R set
Example: T
= 20 °C T
R set
∆ Tv
= 3 x ( 20 °C - 18 °C) = 6 K
Result: The feed temperature is increased by 6 K.
The higher the selected room influence, the
greater the influence of the room temperature
on the feed temperature.
34
= ∆ T
= PI
= T
– T
)
R act
= 18 °C PI = 3
R act

Set maintenance period

With maintenance, it is a question of a
"reminder function".
 Confirm SERVICE by pressing OK.
The display shows MONTHS BEFORE
v
NEXT SERVICE.
 Use the + or – keys or the rotary control
R set
to enter the value and confirm by
R act
pressing OK.
SERVICE
MONTHS BEFORE
NEXT SERVICE
12
Tabla de contenido
loading

Este manual también es adecuado para:

8509132

Tabla de contenido