Technical Specifications - STEINEL PROFESSIONAL IR CM COM1-24 Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

DIM-24 Multiple Sensor Wiring
1 0.
5
IR CM DIM-24
The leads consist of seven wires:
DT CM DIM-24
1. 24V Input (RED)
2. Control Return (BLUE)
18 AWG wire is recommended
3. Communication (BROWN)
for low voltage sensor & power
4. Switch Input (GREEN)
pack connection.
5. 24V Common (BLACK)
6. +10V dimming ballast input (VIOLET)
7. -10V dimming ballast input (GRAY)
Neutral
Load
Hot
Power Pack
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Gray (Momentary Switch)
Note: Power Pack must be in Auto mode.
Additional wiring diagrams available at www.steinel.net.
Control Pro
Control Pro
DIM-24
DIM-24
(Master)
(Auxiliary)
Presence Detector
Presence Detector
- 16 -

Technical Specifications

Dimensions (L x W x D)
4.72 x 2.76 x 4.21 inches / 120 x 70.2 x 107 mm
Power supply:
IR CM COM1-24
IR CM COM2-24
IR CM DIM-24
DT CM COM1-24
DT CM COM2-24
DT CM DIM-24
Maximum load:
Control output (Blue) 1 A @ 24 VDC/VAC 50/60 Hz
Control output (Blue) 1 A @ 24 VDC/VAC 50/60 Hz
HVAC dry contacts: Common (Yellow)
- Normally open (Yellow/Red)
- Normally closed (Yellow/Black) 1 A @ 24 VDC/VAC 50/60 Hz
Control output (Blue) 1 A @ 24 VDC/VAC 50/60 Hz
1 - 10 volt dimming output (Purple & Gray)
100 mA, max. 50 (1 - 10 V electronic dimming ballasts)
Ultrasonic detection zones:
(Coverage at 2.5 m /
Presence (ft) max. of 22 ft. (426 sq.ft.)
9 ft installation height)
min. 20%
Presence (m) max. of 7 m. (130 sq.m.)
min. 20%
Radial max. of 38 ft. (1236 sq.ft)
max. of 11.5 m (376 sq.m.)
Tangential max. of 26 ft. (718 sq.ft.)
max. of 8 m (218 sq.m.)
PIR detection zones:
Presence (ft.) max. of 22 ft. (440 sq.ft.)
Presence (m.) max. of 7 m. (134 sq.m.)
Radial (ft.) max. of 26 ft. (655 sq.ft.)
Radial (m.) max. of 8 m. (200 sq.m.)
Tangential (ft.) max. of 82 ft. (5290 sq.ft.)
Tangential (m.) max. of 25 m. (1612 sq.m.)
Light level setting:
10 - 1000 lux / 1 - 100 fc.
Time setting:
Control output
30 sec. - 30 min.
Pulse mode (approx. 2 sec. 'ON' 8 sec. 'OFF') - for time delay relay
(only in COM1-24 & COM2-24)
IQ mode (automatic adjustment to the usage profile)
HVAC dry contacts (only in COM2-24)
0 sec. - 10 min. switch 'ON' delay
1 min. - 30 min. stay 'ON' time
Auto-HVAC mode
Installation height:
8 - 12 ft / 2.5 - 3.5 m
Environment:
IP 20 - For indoor use only
Sensor technology:
PIR (Passive Infrared), Single pyro, 11 detection levels,
520 switching zones
Ultrasonic 40 kHz
Protection class:
Class 2
Temperature range:
32° F to 131° F / 0° C to +55° C
Certifications:
UL & CUL Listed,
RoHS & California Compliant
18 - 24 VDC/VAC (20 mA) 50/60 Hz
18 - 24 VDC/VAC (29 mA) 50/60 Hz
18 - 24 VDC/VAC (27 mA) 50/60 Hz
18 - 24 VDC/VAC (32 mA) 50/60 Hz
18 - 24 VDC/VAC (40 mA) 50/60 Hz
18 - 24 VDC/VAC (39 mA) 50/60 Hz
1 A @ 24 VDC/VAC 50/60 Hz
- 17 -
Tabla de contenido
loading

Tabla de contenido