Installation Precautions; Installing The Enclosure - Bosch FPM-1000-ENC Guia De Instalacion

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6
en

Installation Precautions

To avoid incorrect installation and operation, strictly observe the following precautions:
NOTICE!
Follow all instructions in this manual. Do not deviate.
Comply with all codes and standards set forth by the Authority Having Jurisdiction (AHJ).
Do not assume any installation details not shown in this manual.
Do not alter any mechanical or electrical features of the equipment supplied.
Ensure that the environmental conditions of the mounting location comply with the technical
specifications listed in Section Technical Data on Page 7.
Mount to a minimum of 3/8 inches plasterboard (Drywall) with stud spacing less then
24 inches on center. Wall anchors must be used that support at least 110 lbs (50 kg).
Ensure that there is sufficient room to open the cabinet door and dead front door fully, and to
easily install, wire and maintain the panel.

Installing the Enclosure

The cabinet can be either semi-flush or surface mounted.
Depending on the configuration and the battery selection, the FPA-1000-UL can weigh more
than 55 lbs. (25 kg). When attaching the enclosure to a surface, use mounting hardware (not
supplied) capable of supporting this weight, and reinforce the wall as necessary.
Observe position of knockouts for wire entrances:
-
-
Legend Figure 1, Page 3
A
B
1
2
Surface mounting
The enclosure mounts using one hole mounting located at the top of the back box (refer to
Figure 1, Page 3, Item 1), and two securing holes located in the lower section (refer to
Figure 1, Page 3, Item 2).
1.
2.
3.
4.
5.
6.
Semi-flush Mounting with Trim Ring
The FPM-1000-SFMK Semi-flush Mounting Kit includes a trim ring and mounting hardware.
For semi-flush mounting between studs, use the three holes on each side of the enclosure for
the screws (refer to Figure 2, Page 4, Item 1).
Use four screws to fasten the trim ring (refer to Figure 2, Page 4, Item 2).
NOTICE!
In a semi-flush mounting of the enclosure, if the screws are overtightened or the enclosure is
set too deep, the trim ring might not fit properly. The sides of the enclosure might need shims
to tighten the gap.
F.01U.133.409 | 2.0 | 2011.08
two knockouts on top
one knockout on right side.
Top view, with 2 knockouts
Right side view, with 1 knockout
Hole mounting
Securing holes
Using the enclosure as a template, mark the top mounting hole on the mounting surface
(refer to Figure 1, Page 3, Item 1).
Start the mounting screw (not supplied) for this hole.
Slide the enclosure onto the screw so that the screw moves up into the thinner section of
the hole.
Tighten the screw.
Tighten the two bottom screws.
Knock out the desired wire entrances on the enclosure (refer to Figure 1, Page 3).
FPM-1000-ENC
Bosch Security Systems, Inc.
Tabla de contenido
loading

Tabla de contenido