4.0 CONTROLS AND INDICATION LAMPS

External Control Console.
a. MAINS LAMP - RED - Illuminates whenever the electrical supply to the
dehumidifier is on.
b. FAULT LAMP - AMBER - Illuminates if the internal limit switches detect a
problem, or if the external interlock facility is open circuit.
c. DEFROST - WHITE - Illuminates whenever the dehumidifier is in defrost
mode, this will happen at lower air temperatures and is not a fault condition,
the dehumidifier will revert to normal run automatically when the defrost cycle
is complete.
d. ON/OFF SWITCH - This will only be found on DH150 models and should
always be used if for some reason the dehumidifier is not required to be
running or prior to isolating the dehumidifier from the mains electrical supply.
e. STANDBY SWITCH - This will only be found on DH300/600 models and
must always be used if for some reason the dehumidifier is not required to be
running or prior to isolating the dehumidifier from the mains electrical supply.
IMPORTANT - On initial start up or if the mains electrical supply has been
interrupted for any length of time (greater than 1 hour), then the standby
switch must be set to "standby" before the mains electrical supply is
reinstated, the dehumidifier must be left in this condition for 12 hours before
normal run is selected on the standby switch.
12
Internal Controls.
f. An adjustable internal humidistat effects control of humidity. Range 20/80%.
A normal setting is 60% for achieving comfortable conditions and minimising
condensation. (20% setting will remove more moisture from the dehumidified
space than a 80% setting).
g. An adjustable thermostat effects control of the air temperature and should be
set to the maximum desired air temperature for the dehumidified space.
h. Fan mode switch. This gives the user the option of having the fan cycle
under control of the humidistat (with the compressor), or the fan can run
continuously which will promote better air circulation which again helps to
reduce condensation by preventing stagnant air pockets.
i. If the Turning Hood Top Box Heater assembly option is fitted, then the
adjustable air temperature thermostat control, located on the side of the Top
Box Heater assembly should be set to the desired minimum air temperature
required.