6) What to do if...
Even if the anemometer turns at a speed exceeding the pro-
grammed level, the motors do not carry out the "up" com-
mand ( ) .
Check the voltage supplied to the sensor connection terminals, it should
correspond to the nominal value. If you measure a different value, check
the connections, see whether the motor is running; make sure you have
memorized the sensor code in each motor or control unit you wish the
sensor to control.
Though the connections are OK and the voltage reading on
the sensor connection is correct, when the anemometer turns
the "up" manoeuvre ( ) is not carried out.
The WIND protection cut-in level must be exceeded for at least 3 sec-
onds; make the anemometer turn at an appropriate speed; you could try
lowering the WIND protection cut-in level of the sensor; check the flash-
ing of the RED LED, indicating that the command is transmitted.
7) Technical characteristics
General characteristics
Mains power supply
Transmission Frequency
Radiated Power
IP protection
Operating temperature
Container
Sensor characteristics
Anemometer
Luxmeter
Nice S.p.a. reserves the right to modify its products at any time.
VOLO S RADIO
VOLO S RADIO/V1
433.92 MHz
Approx. 1 mW (e.r.p.)
IP 34
-20 °C ÷ +55 °C
Dimensions
W = 120 mm
L
= 215 mm
H
= 85 mm
Weight
P
= 250 g
Range
Resolution
Conversion constant
Accuracy
Programmable levels
Range
Resolution (KLux)
Accuracy
Programmable levels
The WIND response test has been carried out successfully,
unlike the SUN response test.
The SUN protection "down" manoeuvre is ordered only once when the
programmed level is exceeded for at least 2 minutes. Try switching the
motor and sensor off and back on again, then repeat the test. You could
also try lowering the SUN protection cut-in level. Check the flashing of
the GREEN LED, indicating that the command is transmitted.
The sensor is working but its radio range is inadequate.
Make sure that there are no other devices operating at the same fre-
quency and with continuous transmission, such as alarms, headphones,
etc., which might reduce the range.
230 Vac 50/60 Hz 1.5W
120 Vac 50/60 Hz 1.5W
LPD device with incorporated aerial
Under optimum conditions it corresponds to a range of approx. 100-200m
L
0-127 Km/h
1 Km/h
Rev / s
0.26
Km / h
± 2 % F.S.
Level 1 = 5 Km/h
Level 2 = 10 Km/h
Level 3 = 15 Km/h
Level 4 = 30 Km/h
Level 5 = 45 Km/h
0 ÷ 64 KLux
0 - 10 KLux: 0.25 KLux
10 - 40 KLux: 0.5 KLux
40 - 64 KLux: 1 KLux
± 10% F.S.
Level 1 = 2 KLux
Level 2 = 5 KLux
Level 3 = 10 KLux
Level 4 = 20 KLux
Level 5 = 40 KLux
Level 6 = AUTO
Level 7 = DELETE
GB
5