European Directive

CE Low Voltage Directive Compliance

2014/35/EU

EMC Directive

2014/30/EU
Machinery Directive
2006/42/EC
The customer must display the CE Mark on the final device containing this product. Customers
must verify that the final device complies with EU standards.
CE Low Voltage Directive Compliance
It has been confirmed that this product complies with the CE Low Voltage Directive by
conducting a test according to IEC/EN 61800-5-1:2007.
The following conditions must be satisfied for machines and devices incorporating this product
to comply with the CE Low Voltage Directive.

Area of Use

Install this product in a location with Overvoltage Category III and pollution degree 2 or less as
specified in IEC/CE 60664.

Connect a Fuse to the Input Side (Primary Side)

The drive circuit protection must comply with IEC/EN 61800-5-1:2007 for protection against a
short circuit in the internal circuitry. Connect semiconductor fuses on the input side for branch
circuit protection.
Refer to
Single-Phase 200 V Class on page
Three-Phase 400 V Class on page 281
WARNING
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not
immediately energize the drive or operate peripheral devices. Wait for the time specified on the warning label at a
minimum and make sure that all indicators are OFF. Then check the wiring and peripheral device ratings to find
the cause of the problem. If you do not know the cause of the problem, contact Yaskawa before you energize the
drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral devices, it can
cause serious injury or death.
EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side to
comply with the EMC Directive.
Drives with built-in EMC filters (models 2xxxE, BxxxE, 4xxxE) were tested in accordance with
European standard IEC/EN 61800-3:2004/A1:2012, and comply with the EMC Directive.

Wire Selection

Select the correct wires for main circuit wiring.
Refer to
Main Circuit Wire Gauges and Tightening Torques (for CE Standards) on page 283
wire gauges and tightening torques as specified by European standards.
Refer to
Main Circuit Wire Gauges and Tightening Torques (for UL Standards) on page 296
wire gauges and tightening torques as specified by UL standards.
30
Table 1.6 Harmonized Standard
IEC/EN 61800-5-1:2007
EN 61800-3: 2004+A1:2012
• EN ISO 13849-1:2015 (PL e (Cat.III))
• IEC 62061(ed.1);am1;am2 (SILCL3)
• EN 62061:2005/A2:2015 (SILCL3)
• IEC/EN 61800-5-2:2016
280,
Three-Phase 200 V Class on page
for more information. About recommended fuses.
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction