Use this form as a guide for your store's checklist on the following page.
Store: QT Market
Date: 7/30/2018
Unit
Model Number
Serial Number
Factory Order Number
Manufacture Date
Defrost
Circuit NO.
Type
No./Day
Length
Superheat
Suction Set Point
Suction Pressure
Suction Temperature
Split/Satellite Superheat
Suction Set Point
Suction Pressure
Suction Temperature
Oil
Oil Separator
Pressure Differential
Condenser
Head Pressure
Water Temperature In
Water Temperature Out
Refrigerant
Receiver Level
Liquid Sight Glass
Compressor No.
Model No.
Discharge Temperature
Amp Draw
Shell Temp at Oil Connect
Float or Oil Connect
Oil Control Magnet Cond.
Controller
Alarms
Time & Date Displayed
Sample Proto-Aire EZ Checklist
Location: Anytown, USA
Time:
A
07/30/2018
1
2
3
Off
Off
Off
2
3
3
40m
45m
45m
26°
52 psig
52.0 psig / 17°F Saturated
17°
POE
Between Glasses
214.9 psig
OK
OK
448a
Foamy
1
2
ZBD57KCE ZB57KCE
173
166
10.2
10.7
hot
hot
¾
¾
Notes:
L.L. Filter changed
All TXV valves adjusted.
Raised suction S.P. from 48 psig to 52 psig. All cases are cleaned.
4
5 / 6
Off
Off /
2
1 /
45m
60m /
3
ZB57KCE
166
10.8
warm
¾
25
3090249_D