Fancoil
failure
status
(PLC:41615)
Protection status
(PLC:41616)
Baud rate
(PLC:41641)
Check digit
information
(PLC:41642)
Stop bit
information
(PLC:41643)
1614
Bit14
EE water level detection failure
Bit8
E8 fan speed detection is out of control
Bit7
E7 EEPROM error
Bit4
E4 T2B sensor failure
Bit3
E3 T2A sensor failure
Bit2
E2 T1 sensor failure
Except for the 2 bits above, other bits in this byte are 0. This byte is
read only.
1615
Bit1
P1 protection against cold or defrosting
Except for the 1 bit above, other bits in this byte are 0. This byte is read
only.
1640
The following baud rate
support is available:
4800
9600
19200
38400
1641
No parity: 0x02
Odd parity: 0x01
Even parity: 0x00
1642
One stop bit: 0
Two stop bits: 1
50
After changing these three
parameters. The next time
you communicate. Need to
correspond to the modified
serial port configuration.
Otherwise the
communication will not be
successful. After powering
up again. Revert to the
default settings:
9600BPS /NO CHECK/ONE
STOP