ASTRALPOOL CDP LINE V2
4.6.
HOT WATER BATTERY
This is an optional, present on the following models: CDP2+W (65895), CDP3+W (65896),
CDP4+W (65897) & CDP5+W (65898).
This optional is used to provide the appliance an extra heating mechanism via boiler or any
other hot water source.
The connection is located on the upper right side of the machine: It is a ½'' male theaded
fittings.
See IMAGES 6 (pg. 92) for further details.
Hot water supply must be at least 45ºC and no more than 90ºC.
Maximum pressure on the water circuit must not exceed 0,3 MPa (3 bar).
Hot water source must enter the appliance on the top tubing.
4.7.
ELECTRICAL HEATING BATTERY
This is an optional, present on the following models: CDP2+E (65899), CDP3+E (65900), CDP4+E
(65901) & CDP5+E (65902).
This optional is used to provide the appliance an extra heating mechanism via internal electric
air heating elements.
4.8.
ACCESS TO TECHNICAL COMPARTMENT
See IMAGES 7 (pg. 93) to see the front cabinet disassembly to perform the power supply
connection.
4.9.
ELECTRICAL SCHEME
Images 8 describe the connection diagrams for display and temperature & humidity probe.
Then the internal appliance electrical scheme is shown. See IMAGES 8 (pg. 98).
5. START UP OF THE UNIT
5.1.
UNIT CONTROLLER (PLC)
5.1.1. PLC I/O
TABLES 3 (pg. 80) describes the analog and digital inputs / putputs of the controller and its
meaning.
5.1.2. PLC ICONS
TABLES 4 (pg. 81) describe the icons present in the user interface and its meaning.
5.1.3. PLC ALARMS
TABLES 5 (pg. 83) Describe the alarms that can be present in the appliance.
5.1.4. USER INTERFACE
Pressing and holding "SET" key for 3 seconds will switch on or off the appliance.
Right side of the display shows ''OFF'' when the unit is OFF and the ambient temperature when
the unit is ON. Left side of the display shows time when the unit is OFF and the ambient relative
humidity when the unit is ON.