Mitsubishi Electric CITY MULTI PAC-PH01EHYU-E Manual De Instalación página 24

Tabla de contenido
In case of collective installation and continuous installation
• When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through, ample
space between blocks of units, and sufficient space for airflow. (The areas marked with [A] in the figures below must be left open.)
• In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to
L1, L2, and L3 as shown in the tables below.
• If there are walls in the front and rear of the block of units, up to six units (three units for units P168, EP168, and EP192) can be installed
consecutively side by side, and a space of 1000 mm (39-3/8 in) or more must be left between each block of six units (three units for unit P168,
EP168, and EP192).
(1) Side-by-side installation
When the distances between the units (L4)
need to be small
[A]
L4
Unit height
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
450 (17-3/4) +h1
450 (17-3/4) +h2
(2) Face-to-face installation
When there are walls in the front and rear of
the block of units
[A]
h1
Unit height
L1
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
450 (17-3/4) +h1
300 (11-13/16) + h2
(3) Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of
the block of units
[A]
h2'
Unit height
Required minimum distance [mm (in)]
L2 (Rear)
L2' (Rear)
450 (17-3/4) +h2
450 (17-3/4) +h2'
[A]: Leave open in two directions.
24
h2
Unit height
h1
L2
[A]
L1
L4 (Between)
30 (1-3/16)
h2
Unit height
L2
L4
[A]
L4
L4 (Between)
450 (17-3/4)
h2
Unit height
L2
L4
[A]
L2'
L4 (Between)
900 (35-7/16)
When the distance behind the block of units
(L2) needs to be small
[A]
L4
Unit height
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
450 (17-3/4) +h1
300 (11-13/16) + h2
When there is a wall on either the right or left
side of the block of units
h3
Unit height
L3
Required minimum distance [mm (in)]
L3 (Right/Left)
L4 (Between)
30 (1-3/16) + h3
450 (17-3/4)
When there are two walls in an L-shape
h3
Unit height
L3
[A]
Required minimum distance [mm (in)]
L2 (Rear)
L3 (Right/Left)
450 (17-3/4)
1000 (39-3/8) + h3
[mm (in)]
h2
Unit height
h1
L2
[A]
L1
L4 (Between)
450 (17-3/4)
L4
L4
h2
Unit height
L2
[A]
L4
L4 (Between)
900 (35-7/16)
Tabla de contenido
loading

Este manual también es adecuado para:

City multi pac-ph02ehyu-eCity multi pac-ph03ehyu-e

Tabla de contenido