A
MOUNTING
n For exact determination of wind and brightness direction the Weather
Station must be mounted in north alignment (N).
The place where the sensor is installed might have an impact on the
measured values.
[1] Façade mounted versions
[2] Roof mounted version
1
Mounting with Somfy accessories (
2
Mounting on already existing mast Ø 25 mm.
3
Mounting on already existing mast Ø 50 mm with Bracket for
4
Weather Station (
).
[3] n Weather Station must always be installed upright, not horizontal
or in an angle.
CHARACTERISTICS
Weather Station M10/M25
Supply voltage
Max. current
Operating temperature
Material of housing
Housing dimensions (h, Ø)
Weight
Protection class
Degree of protection
Conformity
Accessories
Mast Adaptor
for Weather Station
Ref. 1860321
Dimensions
H: 90 mm/Ø 25 - 50 mm
Sensors
M10
Wind speed
Wind direction
Brightness
Global radiation
Vertical radiation
(0°, 45°, 90°, 135°, 180°, 225°, 270°, 315°)
Twilight
Temperature
Humidity sensor
Precipitation
CABLE
Connection to ...
Power Supply
RS485 Bus
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
7/20
- animeo Connect . Connect Weather Station . Ref. 5137979C
1-3
) on a mast Ø 50 mm.
24 V DC + 10 %/- 30 %
230 mA@24 V
- 30° C...+ 70° C
Polycarbonate
105 mm, 103 mm
162 g
IP44 in working position
www.somfy.com/ce
Metallic Mast
1
Ref. 1860335
H: 1 m/Ø 50 mm
M25
Measuring Range
0...35 m/s
1...360°
)
0...100 kLux
(x8)
(x4
)
) 0...1,200 W/m
2
(x1
(x1
) 0...1,200 W/m
2
(x8
0...1 kLux
- 30...+ 50° C
0...100 % rel. humidity
1/0 (precipitation yes/no) Thermal output, sensor dry, bedewing protection: 0.1 W
Cable
Min.: 2 x 0.3 mm
/22 AWG / Max.: 2 x 0.5 mm
2
Min.: 2 x 0.3 mm
/22 AWG / Max.: 2 x 0.5 mm
2
B
WIRING
n Use rigid cable.
n If a hole has been drilled in the mast during installation of the
unit to fit the cable through, the cable may be damaged by sharp
edges.
m The cable for connection of the Weather Station must be suitable
for permanent outdoor use and compliant to the relevant standards.
7 minutes after switching on the device, the flashing LED indicates
normal operation.
C
TOPOLOGY
A.
„xx" represents the bus system handled by the gateway, e.g. io,
SDN, ...
Not compatible with PoE switch.
Wall Mount Bracket
2
Ref. 1860336
200 x 90 x 30 mm (w x d x h)
Resolution
Accuracy
0.1 m/s
± 5 % (± 1 m/s) rms over 360°
± 5° with laminar flow and windspeed > 2 m/s
± 200 Lux with < 2 kLux; ± 10 % with ≧ 2 kLux
0.1 kLux
1 W/m
± 15 W/m
2
1 W/m
± 15 W/m
2
1 Lux
± 20 Lux with < 100 Lux; ± 20 % with ≧ 100 Lux
0.1° C
± 1° C with laminar flow and windspeed > 2 m/s
0.1 % rel. humidity
± 10 % rel. humidity at 20° C and wind speed > 2 m/s
Thermal output, sensor wet, drying phase: 1.1 W
Twisted pair
/20 AWG Required
2
/20 AWG Required
2
Bracket
3
4
for Weather Station
Ref. 1860320
180 x 80 x 80 mm
; ± 15 % with ≧ 100 W/m
with < 100 W/m
2
2
; ± 15 % with ≧ 100 W/m
with < 100 W/m
2
2
Max. length
150 m / 300 m
150 m / 300 m
2
2