1. EXPLANATION OF SYMBOLS AND SAFETY INSTRUCTION
1.1. Explanation of symbols
CAUTION! - Important recommendation or warning
EN
concerning safety conditions during installation and
operation of the heating boiler
DANGER! - fault or improper use may cause injury or
be hazardous to the life of humans or animals.
FIRE HAZARD! - fault or improper installation and
operation may cause fire.
INFORMATION - Important information on the proper
operation of the product.
1.2. Requirements to boiler installation room
This manual contains important information for the safe and
correct installation, start-up and trouble-free operation and
maintenance of the heating boiler.
The heating boiler can be used for heating rooms only in the
manner described in this manual.
Take note of the boiler type information indicated on the
factory sticker and the technical data provided in chapter 12
in order to ensure proper operation of the product.
1.2.1. Instructions to boiler installer
During installation and operation, the country-specific
requirements and regulations must be observed:
• local construction regulations on installation, air supply
and exhaust gas extraction as well as chimney connection.
• regulations and norms concerning the fitting of the
heating installation with safety devices.
Use only original BURNiT parts
DANGER of intoxication, suffocation.
Inadequate inflow of fresh air to the boiler room
may result in dangerous leak of exhaust gases
during boiler operation.
- Make sure the air inlets and exhaust gas outlets are
not clogged or closed.
- If faults are not remedied immediately, the boiler
must not be operated, and the user must be
provided with written instructions on the fault and
the hazard it entails.
DANGER of fire when burning flammable
materials or liquids.
- Flammable materials/liquids must not be left in
close proximity of the heating boiler.
- Instruct system user of the allowed minimum
clearances from surrounding objects.
Customer
*
maintenance training by authorized installer/
service shop.
It is mandatory to assure a backup power generator
*
of corresponding rated power! (see 12.2)
1.2.2. Instructions to installation user
Customer
*
maintenance training by authorized installer/
service shop.
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
must
undergo
boiler
must
undergo
boiler
DANGER of intoxication or explosion
Toxic gases may be discharged when burning
waste, plastics, liquids.
$
- Use only the fuels indicated in this manual.
- In case of danger of explosion, ignition or discharge
of exhaust gases in the room, stop the heating
boiler from operation.
CAUTION! Danger of injury / damage of system due
to incompetent operation.
- The heating boiler must be serviced only by persons
familiar with the operation manual.
*
- As a user, you are only allowed to start the boiler
up, adjust the temperature of the boiler, shut the
boiler down and clean it.
- Unattended children must not be allowed access to
premises with running pellet burner inside.
It is mandatory to assure a backup power generator
*
of corresponding rated power! (see 12.2)
- Operate the heating boiler at a maximum temperature of
80°C, and to that end you must regularly inspect the boiler
room.
- Do not use flammable liquids for ignition or increase the
fire or increase boiler's output .
- Collect ash in lid-covered fireproof containers.
- Clean the heating boiler surface using non-flammable
agents only.
- Do not place flammable objects onto the heating boiler or
in its proximity. (see diagram 1 for the minimum clearances)
- Do not store flammable materials in the boiler room.
1.2.3.
Minimum
combustibility of construction materials
The applicable minimum clearances in your country may
differ from the ones specified bellow. Please, consult your
installer.
The minimum distance from the heating boiler or exhaust
gas pipe to objects or walls must be at least 200 mm.
For general safety considerations, we recommend that the
boiler be placed on a foundation with height of 100 mm
made of class A material, see table 1.
Diagram 1. Recommended clearances between the
Table 1. Combustibility of construction materials
Class А - non-
combustible
Class B
operation/
- hard
combustible
Class С1/С2 -
Medium
combustible
Class C3
- easy
combustible
operation/
4
Safety rules for user operation:
clearances
for
boiler and walls /see page 68/
Stone, bricks, ceramic tiles, baked clay,
solutions, plaster free of organic additives.
Gypsum board panels, basalt fiber needled
felt, fiberglass board, AKUMIN, Izomin,
Rajolit, Lignos, Velox, Heraklit.
Wood beech, oak
Wood softwood, layered wood
Asphalt,
cardboard,
fiberboard,
cork,
polyethylene.
installation
and
cellulose,
tar,
polyurethane,