FUNCTIONAL SPECIFICATIONS AC Smart BACnet
59

Initialization at the Start Up

The system is designed to automatically recognize the connected air conditioners. Therefore, a
period of approximately one minute will be required to recognize all the air conditioners after the
system is turn on. During this period, the following error PDU may be returned when an object
corresponding to an air conditioner is accessed.
ErrorClass = Object; ErrorCode = Unknown_Object
If an attempt is made to read the Object List property of the Device object from an air conditioner
during the above period of recognition, the following error PDU will be returned, unless the air
conditioner has been recognize:
ErrorClass = Device; ErrorCode = Configuration_In_Progress
Communication error response of AC Smart BACnet , please refer to refer to AC Smart BACnet
Error Response Table on page 70AC Smart BACnet Error Response Table on page 69.

Clock Setting

The Timesynchronization service allows clock settings by the local time.
Furthermore, the UTCTimesycchronization allows clock settings by UTC