Electrical connections and selections
OPERATING OPTIONS
The detector's operating options are set using the DIP switches:
DIP switch 1:
WALK-TEST EXCLUSION
OFF: walk-test activated (default)
ON: walk-test excluded
DIP switch 2:
LED EXCLUSION
OFF: LED switch-on activated (default)
ON: LED switch-on excluded
DIP switch 3:
NUMBER OF ALARM IMPULSES SELECTION
OFF: 2 impulses in 8 seconds (default)
ON: 4 impulses in 8 seconds
DIP switch 4:
DETECTOR REMOVAL ALARM EXCLUSION
OFF: alarm removal activated (default)
ON: alarm removal excluded
WARNING: to increase the battery life it is recommended to disable the signal indicators: the
autonomy is reduced by 10% with the walk-test indicator inserted.
USER INSTRUCTIONS