Tabla 4- 1
Tipos de puntos de datos soportados, grupos de objetos, variantes y tipos de datos S7 compatibles
Formato (memoria
necesaria)
Bit
Integer (16 bits)
Integer (32 bits)
Número en coma flotante (32 bits)
Número en coma flotante (64 bits)
Bloque de datos (1 ... 64 bytes)
34
Tipo de punto de datos (grupo de
objeto) [variations]
Binary Input (1) [1, 2]
Binary Input Event (2) [1, 2]
Binary Output (10) [2]
1)
Binary Output Event (11) [1, 2]
Binary Command (12) [1]
Counter Static (20) [2]
Frozen Counter (21) [2, 6]
Counter Event (22) [2, 6]
Frozen Counter Event (23) [2, 6]
Analog Input (30) [1]
Analog Input Event (32) [2, 4]
Analog Output Status (40) [2]
Analog Output (41) [2]
Analog Output Event (42) [2, 4]
Counter Static (20) [1]
Frozen Counter (21) [1, 5]
Counter Event (22) [1, 5]
Frozen Counter Event (23) [1, 5]
Analog Input (30) [2]
Analog Input Event (32) [1, 3]
Analog Output Status (40) [1, 3]
Analog Output (41) [1]
Analog Output Event (42) [1]
Analog Input (30) [5]
Analog Input Event (32) [5, 7]
Analog Output Status (40) [3]
Analog Output (41) [3]
Analog Output Event (42) [5, 7]
Analog Input (30) [6]
Analog Input Event (32) [6, 8]
Analog Output (41) [4]
Analog Output Event (42) [6, 8]
5)
Octet String (110) [ - ]
Octet String Event (111) [ - ]
Sentido:
in / out
in
in
out
out
1)
out
in
in
2)
in
in
3)
in
in
out
4)
out
out
4)
in
in
2)
in
in
3)
in
in
out
4)
out
out
4)
in
in
out
4)
out
out
4)
in
in
out
out
4)
in
in
5)
Instrucciones de servicio, 07/2013, C79000-G8978-C312-01
Tipos de datos S7
Área de operandos
BOOL
I, Q, M
BOOL
I, Q, M
BOOL
BOOL
BOOL
I, Q, M
UINT, WORD
I, Q, M
UINT, WORD
I, Q, M
INT
I, Q, M
INT
I, Q, M
INT
I, Q, M
UDINT, DWORD
I, Q, M
UDINT, DWORD
I, Q, M
DINT
I, Q, M
DINT
I, Q, M
DINT
I, Q, M
REAL
Q, M
REAL
Q, M
REAL
Q, M
LREAL
Q, M
LREAL
Q, M
LREAL
Q, M
I, Q, M
5)
I, Q, M
5)