BExDS110D
24V DC
BExDS110D
12V DC
BExDS110D
48V DC
BExDS110D
230V AC
BExDS110D
110V AC
BExDS110D
115V AC
The above table also shows the maximum voltages at which
the sounders can be operated.
9) Cable Selection
Cables must be capable of handling the current drawn from
all of the units on the line.
SAFETY WARNING: If the high output BExDS120D sounders
are used at high ambient temperatures, i.e. over +40ºC, then
the cable entry temperature may exceed +70ºC and therefore
suitable heat resisting cables must be used, with a rated
service temperature of at least 95ºC.
10) Earthing
Both AC and DC sounder units must be connected to a good
quality earth. The units are provided with internal and
external-earthing terminals, which are, both located on the
terminal chamber section of the unit (see figures 2 and 3).
When using the external earth terminal a cable crimp lug
must be used. The cable lug should be located between the
two M5 stainless steel flat washers. The M5 stainless steel
spring washer must be fixed between the outer flat washer
and the M5 stainless steel nut to ensure that the cable lug is
secured against loosening and twisting.
11) Cable Glands
The sounders have dual cable gland entries with M20 x1.5
entry threads. Only cable glands approved for Ex 'd'
applications can be used, which must be suitable for the type
of cable being used and also meet the requirements of the Ex
'd' flameproof installation standard BS EN 60079-14 : 1997.
When only one cable entry is used the other one must be
closed with an Ex 'd' flameproof blanking plug, which must be
suitably approved for the installation requirements.
For combustible dust applications, the cable entry device and
blanking elements shall be in type of explosion protection
increased safety "e" or flameproof enclosure "d" and shall
have an IP 6X rating according to EN 60529.
SAFETY WARNING: If the high output BExDS120D sounders
are used at high ambient temperatures, i.e. over +40ºC, then
the cable entry temperature may exceed +70ºC and therefore
suitable heat resisting cable glands must be used, with a
rated service temperature of at least 95ºC.
12) Cable Connections
See drawing C and D
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. BExDS120D and BExDS110D (Gas-Dust) English
265mA
30V
195mA
15V
130mA
58V
56mA
264V
93mA
121V
110mA
126V
Issue A
Tone Selection and 2nd and 3rd Stage Alarms
13)
See wiring diagram E
Volume Control
14)
See drawing F
End of Line Monitoring (DC Units)
15)
On BExDS120D and BExDS110D DC units, dc reverse line
monitoring can be used if required. All DC sounders have a
blocking diode fitted in their supply input lines. An end of line
monitoring diode or an end of line monitoring resistor can be
connected across the +ve and –ve terminals. If an end of line
resistor is used it must have a minimum resistance value of
3k3 ohms and a minimum wattage of 0.5 watts or a minimum
resistance value of 500 ohms and a min. wattage of 2 watts.
TONE SELECTION TABLE
Tone Selection
Stage 1
Frequency Description
Continuous 1000Hz
1
Toxic Gas Alarm
2
Alternating 800/1000Hz at 0.25s
intervals
3
Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated
4
Sweeping 800/1000 at 1Hz
5
Continuous at 2400Hz
6
Sweeping 2400/2900Hz at 7Hz
7
Sweeping 2400/2900Hz at 1Hz
8
Siren 500/1200/500Hz at 0.3Hz
9
Sawtooth 1200/500Hz at 1Hz
10
Alternating 2400/2900Hz at 2Hz
11
Intermittent
1000Hz
at
General alarm
12
Alternating 800/1000Hz at 0.875Hz
13
Intermittent 2400Hz at 1Hz
14
Intermittent 800Hz 0.25s on 1s off
15
Continuous at 800Hz
16
Intermittent
660Hz 150mS
150mS off
17
Alternating 544Hz
(100mS)/440Hz(400mS)
18
Intermittent 660Hz 1.8s on, 1.8s off
19
1400Hz to 1600Hz sweep up over
1s - 1600Hz to 1400Hz sweep down
over 0.5s
20
Continuous 660Hz
21
Alternating 554/440Hz at 1Hz
22
Intermittent 554Hz at 0.875Hz
23
800Hz pulsing at 2Hz
24
Sweeping 800/1000Hz at 50Hz
25
Sweeping 2400/2900Hz at 50Hz
26
Simulated bell sound
27
Continuous 554Hz
28
Continuous 440Hz
29
Sweeping 800/1000Hz at 7Hz
30
420Hz repeating 0.625s on, 0.625s
off Australian alert signal
31
1200/500Hz at 1 Hz
Prepare to Abandon Platform
32
Sweeping 500/1200Hz 3.75s on,
0.25s off 15Hz
www.e2s.com
(Four Sheets)
25-02-04
DIP Switch
Stage Selection
Settings
1 2 3 4 5
Stage 2
0 0 0 0 0
Tone 31
1 0 0 0 0
Tone 17
0 1 0 0 0
Tone 2
1 1 0 0 0
Tone 6
0 0 1 0 0
Tone 3
1 0 1 0 0
Tone 7
0 1 1 0 0
Tone 10
1 1 1 0 0
Tone 2
0 0 0 1 0
Tone 15
1 0 0 1 0
Tone 7
0.5Hz
0 1 0 1 0
Tone 31
1 1 0 1 0
Tone 4
0 0 1 1 0
Tone 15
1 0 1 1 0
Tone 4
0 1 1 1 0
Tone 2
on,
1 1 1 1 0
Tone 18
0 0 0 0 1
Tone 2
1 0 0 0 1
Tone 2
0 1 0 0 1
Tone 2
1 1 0 0 1
Tone 2
0 0 1 0 1
Tone 2
1 0 1 0 1
Tone 2
0 1 1 0 1
Tone 6
1 1 1 0 1
Tone 29
0 0 0 1 1
Tone 29
1 0 0 1 1
Tone 2
0 1 0 1 1
Tone 26
1 1 0 1 1
Tone 2
0 0 1 1 1
Tone 7
1 0 1 1 1
Tone 32
0 1 1 1 1
Tone 11
1 1 1 1 1
Tone 26
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200
Stage 3
Tone 11
Tone 5
Tone 5
Tone 5
Tone 27
Tone 5
Tone 5
Tone 5
Tone 2
Tone 5
Tone 1
Tone 5
Tone 5
Tone 5
Tone 5
Tone 5
Tone 27
Tone 5
Tone 5
Tone 5
Tone 5
Tone 5
Tone 5
Tone 5
Tone 5
Tone 1
Tone 5
Tone 5
Tone 5
Tone 5
Tone 1
Tone 1
)
(6