ModBUS Register Information
Group Name
Setup/Relay 2
Setup/Relay 2
Setup/Relay 2/Alarm
Setup/Relay 2/Alarm
Setup/Relay 2/Alarm
Setup/Relay 2/Alarm
Setup/Relay 2/Alarm
Setup/Relay 2/Alarm
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Control
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Event
Setup/Relay 2/Timer
Setup/Relay 2/Timer
Setup/Relay 2/Timer
68
Table A-9 Controller ModBUS Registers (continued)
Tag Name
Register # Data Type
Type
40093
Transfer
40094
Setting
High Alarm
40095
Low Alarm
40097
High
40099
Deadband
Low
40101
Deadband
On Delay
40103
Off Delay
40104
Setpoint
40105
Phase
40107
Deadband
40108
Overfeed
40110
Timer
On Delay
40111
Off Delay
40112
Reset
Overfeed
40113
Timer
Setpoint
40114
Phase
40116
Deadband
40117
On Max Time
40119
On Min Time
40120
Off Max Time
40121
Off Min Time
40122
Hold Type
40123
Sensor Select
40124
Hold Mode
40125
Length
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Float
2
R/W
Float
2
R/W
Float
2
R/W
Float
2
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Description
Selects the relay type (0 = Alarm; 1 =
Control; 2 = Status; 3 = Timer; 4 = Event)
Selects the transfer value for the relays
(0 = De-energized; 1 = Energized)
Sets the high alarm setpoint
Sets the low alarm setpoint
Sets the high alarm deadband
Sets the low alarm deadband
Sets the on delay time
Sets the off delay time
Sets the controller setpoint
Sets the controller phase
(0 = Low; 1 = High)
Sets the controller deadband
Sets the overfeed timer value (mins)
Sets the on delay time (sec)
Sets the off delay time (sec)
Resets the overfeed timer
Sets the event setpoint
Sets the event phase (0 = Low; 1 = High)
Sets the event deadband
Sets the max on time (mins)
Sets the min on time (mins)
Sets the max off time (mins)
Sets the min off time (mins)
Sets which Sensor outputs are affected
during timer on time (0 = None;
2 = Selected Sensor; 13 = All Sensors)
Selects which Sensor outputs are being
held/transferred during the timers on time
(this is used when Hold type is set for
single Sensor)
Selects hold outputs vs. set transfer value
during timers on time