3.1 humiSonic (UU0*R)
Range of ultrasonic adiabatic humidifiers for direct humidification
in rooms, with built-in fans for uniform atomised water distribution.
humiSonic is suitable for many applications, such as: the humidification in
production plants, data centres, warehouses, printing facilities, museums,
restoration workshops, theatres, etc., where optimisation of room
humidity is essential in ensuring personal comfort and safeguarding
goods.
3.2 Name/ Part numbers
Part number
Description
UU0(X)R(*)0001 without auxiliary card, without temperature and humidity
probe
UU0(X)R(*)AS01 with auxiliary card and with temperature and humidity probe
(X) = 2 -> 2 kg/h (4.4 lbs/h), 4 -> 4 kg/h (8.8 lbs/h), 6 -> 6 kg/h (13.2 lbs/h),
8 -> 8 kg/h (17.6 lbs/h)
(*) = D -> 230 Vac power supply, 1 -> 110 Vac power supply
3.3 Dimensions and weights
317
Fig. 3.a
Models
UU02
Production kg/h (lbs/h)
2 (4.4)
Width mm (in)
Depth mm (in)
Width A mm (in)
483 (19)
Weight kg (lb)
packaged
11 (24.2)
empty
9.5 (20.9)
installed*
10.3 (22.7) 14.1 (31.1) 17.9 (39.5) 21.7 (47.8)
* in operating conditions, filled with water.
3.4 Opening the packaging
NOTICE Dropping or bumping the humidifier may irreparably damage
its internal components and panelling.
Make sure the package is intact upon delivery and immediately notify
the transporter, in writing, of any damage that may be due to careless
or improper transport;
move the humidifier to the site of installation before removing from
the packaging, grasping the neck from underneath;
open the cardboard box, remove the protective material and remove
the humidifier;
the unit must always be stored in a dry place before installation.
3. GENERAL DESCRIPTION
Tab. 3.a
UU04
UU06
UU08
4 (8.8)
6 (13.2)
8 (17.6)
317 (12.5)
274 (10.8)
608 (24)
733 (28.9)
858 (33.8)
14 (30.9)
17 (37.5)
21 (46.3)
12.5 (27.6) 15.5 (34.2) 18.5 (40.8)
Tab. 3.b
3.5 Material supplied
Check that the following are present:
1. wall-mounting bracket;
2. kit of screws and anchors;
3. 1 cable gland;
4. 4 feet;
5. user manual.
3.6 Preparing for assembly
• The unit is designed to be assembled on a horizontal support or wall
that can support its weight in normal operating conditions (see par.
"Wall-mounting");
• Install the humidifier in a safe place where it cannot be tampered with,
as far as possible from any air flows;
• Position the humidifier horizontally using a spirit level, observing the
minimum clearances in mm (see Fig. 1.b) to ensure the correct flow of
supply air and allow the required maintenance operations.
≥ 500
(19.7")
NOTICE:
the minimum distance at the rear is recommended for assembly
on a horizontal support.
NOTICE :
for installation on a horizontal support/wall:
1. the humidifier takes in air through by the slits at the back/bottom
respectively;
2. the feet/spacers are fitted at the bottom/rear;
3. the fill/drain hoses are attached at the rear/on the bottom;
4. the power cable gland is fitted at the rear/on the bottom;
5. remove the rear bracket for assembly on a horizontal support.
ASSEMBLY ON A HORIZONTAL SUPPORT
3
7
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
≥ 450
(17.7")
≥ 200...300
(19.7")
≥ 500
(19.7")
<0,5°
Fig. 3.b
1
4
1
AIR
2
2
Fig. 3.c
ENG