3.6.2 Temperature Sensor (Multi Compact / MultiPlus Compact)
The temperature sensor supplied with the product may be used for temperature-
compensated charging. The sensor is insulated and must be mounted on the batteries minus
pole. Default output voltages for Float and Absorption are at 25° C. In adjust mode
temperature compensation is disabled.
15.0
14.5
14.0
13.5
13.0
12.5
Volts
12.0
11.5
11.0
10.5
10.0
0
3.6.3 Remote Control panel & remote on/off switch
The product can be operated remotely in two ways.
Use of only an external switch.
With the aid of a remote control panel.
Observe the following when using only an external switch:
Only functions if the switch on the product is switched to the "on" position.
Not to be connected if a remote control is connected.
Observe the following when using a remote control:
Only functions if the switch on the product is switched to the "on" position.
3.6.4 External Alarm Relay and Virtual Switch
An open collector output is available to connect a relay that can be used for remote alarm and
other purposes (a. o. generator start signal).The maximum voltage/current that can be
switched (open collector transistor): 66V 40mA.
The open collector output can be programmed with VEConfigure.
5
10 15 20 25 30 35 40 45 50 55 60
Battery temperature
30
29
28
27
26
Volts
25
24
23
22
21
20