Ups Storage; Electromagnetic Compatibility; Overvoltage Protection; Air Exchange In The Battery Room - ALLTRONIC SEMIS 160 Manual De Instalacion Y Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

UPS S
TORAGE
E
LECTROMAGNETIC COMPATIBILITY
(*) Type of environment defined in EMC regulations
O
VERVOLTAGE PROTECTION
A
IR EXCHANGE IN THE BATTERY ROOM
- example calculation
The air intake/outlet must be located so as to be most favourable to circulation, e.g.:
- openings on opposing walls
- with a minimum distance of 2 m if both on the same wall.
A = 28 x Q = 28 x 0.05 x n x Igas x C10 (1/10³) [cm²]
A = 28 x Q = 28 x 0.05 x n x Igas x C10=28 x 0.05 x 240 x 8 x 120 x 1/10³ = 322 cm
- 67 -
2