FS 10
US 0
EI 0
EO 0
AI 60
AT 10
W NC
V 230
Pd 70
FM
SET.F
Sets the switchover frequency for the
power module.
In case of long power cable, without a
sinusoidal filter, set this value at the
minimum
Sets the interval between two
consecutive automatic "no grip" start-
ups (When the pump will be inoperative
for a long).
Setting the value to "0" disables the
function.
Sets the digital input FUNCTION (clean
contact type)
EI = 0: NO FUNCTION; the input state is ignored
EI = 1: WATER LEVEL; Level signal input with NC logic
EI = 2: EXT ENABLE; Start and disabling by external signal (NC)
EI = 3: PRESS SET 2; enabling the second pressure level SETPOINT2 (NC).
EI = 4: EXTERNAL LEVEL SIGNAL INPUT with NC logic;
EI = 5: ALARM RESET SIGNAL INPUT
Sets the digital output FUNCTION
(clean contact type)
EO = 0: NO FUNCTION; the state of the output is never activated.
EO= 1: ALARM OUTPUT; condition of stop due to fault.
EO = 2: PUMP OPERATING OUTPUT; there is at least one operating pump.
EO = 3: recirculation; activates the relay output time intervals defined by param. AI
Sets the output activation interval (clean
contact type) configured as recycle
function (Eo=3)
Sets the duration of the activation of the
output signal (clean contact type)
Activates communication between two
or more inverters, defining the function
of each unit: MS (MASTER unit) , S1/S2
(SLAVE unit), NC (operation with a
single inverter)
Sets the mains power supply voltage.
230 V for single phase power supply
versions
400V for three phase power supply
versions
Sets the minimum pressure value
(expressed as % of the SET pressure)
that must be reached in no flow,
otherwise an alarm of dry running
Base and Advanced menu will be factory restored. CAUTION: DO NOT USE
THIS FUNCTION in the pumping unit UPV-OS as these models have a
special setting. To reset the factory parameters, press the ENTER key and
hold until "OK" appears on the display (ENTER
****
OK)