15. MQ frequently asked questions
1. What causes the MQ to start?
Answer: The MQ is equipped with both an
internal flow switch and pressure switch. Each of
these can turn the MQ on, depending on water
consumption. The pump will start when:
The flow rate is greater than 0.3 gpm
OR
the pressure is below 29 psi.
2. What causes the MQ to stop?
Answer: Other than the manual on/off button,
only the flow switch is authorized to automatically
stop the MQ during normal operation when flow
drops below 0.3 gpm. The pump will shut off in
12-15 seconds after flow stops.
Additionally, the MQ will be turned off in the event
of a dry-run or overtemperature alarm.
3. What is the maximum height of a tap above
the MQ?
Answer: If a tap or faucet is installed at heights
greater than 50 ft above the MQ, there is the
potential risk that the MQ will never start. In
cases where the MQ starts due to low pressure
(low flow rates), the pressure has to fall below
the pressure switch activation point (28-30 psi
factory setting). To allow for the pressure of 50 ft
of water, tolerances and a safety margin, we
recommend a maximum height of 50 ft between
the MQ and any tap.
4. What is the purpose of the built-in pressure
tank?
Answer: The built-in pressure tank comes from
the factory, pressurized at approximately 23 psi
(with the pump pressure at zero) and holds a
volume of 14 ounces of water. It is designed to
minimize motor startup due to small leaks.
5. How is the dry-run condition determined?
Answer: The dry-run alarm is declared when the
motor is running AND the flow rate is less than
1.6 gpm AND when pressure is less than the
pressure switch setting. When this condition lasts
for 12 seconds, the alarm will be declared after
1 minute, and the motor is stopped. The MQ
attempts to automatically restart every 30
minutes for a maximum of 24 hours. If more than
24 hours pass without water, the pump must be
restarted manually.
16
6. What is the maximum inlet pressure allowed
in the MQ?
Answer: For both MQ 3-35 and MQ 3-45, the
maximum internal pressure allowed is 109 psi.
The maximum inlet pressure when added to the
MQ pressure must not exceed 109 psi.
Remember that inlet pressure adds to the MQ
pressure, so with a 40 psi inlet pressure supplied
to the MQ 3-45, internal pressures can reach
approximately 105 psi (65 + 40 psi).
Additionally, if inlet pressures exceed the built-in
pressure switch activation point (28-30 psi
factory setting), the pressure switch will be
unable to activate, and the ability to turn the MQ
on at low flow rates will be lost. In this situation,
only the flow switch will be able to turn the MQ on
at flow rates above its activation point of 0.3 gpm
7. What is the priming capacity of the MQ?
Answer: Approx. 1.2 gallons.
8. How is overload temperature/overtemperature
of the MQ detected?
Answer: The motor has a thermal switch
incorporated in the motor windings. The switch
will cut out the motor and start again. See the
table below.
Thermal protection
[V]
115
Cut-out
230
Cut-in
Both
9. Where can a pressure gauge be easily
installed to measure the discharge pressure?
Answer: In the discharge piping or in 3/8" GAS
straight thread opening used to add priming
water to the pump.
16. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
[°F]
[°C]
302
150
275
135
151
65-67
Subject to alterations.