English-2
Mounting Considerations
• Mount the drive upright on a flat, vertical and level surface.
Frame
B
C
• Protect the cooling fan by avoiding dust or metallic particles.
• Do not expose to a corrosive atmosphere.
• Protect from moisture and direct sunlight.
Minimum Mounting Clearances
See page 20 for mounting dimensions.
RUN
REV
FAULT
Mounting Option A
No clearance required
between drives.
Ambient Operating Temperatures
Ambient Temperature
Minimum
-10°C (14°F)
(1)
Rating requires installation of the PowerFlex 40P IP 30/NEMA 1/UL Type 1 option kit.
Screw Size
Screw Torque
M4 (#8-32)
1.56-1.96 N-m (14-17 lb.-in.)
M5 (#10-24)
2.45-2.94 N-m (22-26 lb.-in.)
120 mm
(4.7 in.)
Closest object that
RUN
REV
FAULT
may restrict air flow
through the drive heat
sink and chassis
120 mm
(4.7 in.)
Enclosure Rating
Maximum
IP 20/Open Type
40°C (104°F)
IP 30/NEMA 1/UL Type 1
50°C (122°F) IP 20/Open Type
DIN Rail
35 mm
–
120 mm
(4.7 in.)
25 mm
(1.0 in.)
RUN
RUN
REV
REV
FAULT
FAULT
120 mm
(4.7 in.)
Mounting Option B
Minimum Mounting
Clearances
Use Mounting Option A
(1)
Use Mounting Option B
Use Mounting Option B