5 Evolution Operation

5.1 Alarms

Mains presence: signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If the mains is not present > LED goes out
Charger presence : signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If the mains fuse is blown or not present.
If the mains is <98 V or 195 V at 100-150 W.
If the product is out of service
Load presence: Signalled by a green power on LED (no threshold) on the load outputs (no associated report).
If either of the 2 outputs has no voltage, the LED will go out.
Battery presence : signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If the battery is not present:
The battery test is performed in the following manner: every 30 seconds for the first 20 minutes
after commissioning: every 15 minutes after the first 20 minutes. If a fault is detected, the test is
performed every 30 seconds up to 20 minutes after the fault disappears.
Signalled locally by LED not illuminated.
If the battery voltage < 1.85 V/cell ±3 %, signalled locally by a flashing orange LED.
Comment: In the case of C6 and C23 cabinet installation, signaling takes place by a single indicator light:
o
o
o
all OK: green.
mains fault: orange.
battery or charger fault, or load not present: red (this fault takes priority over a mains
fault).
> LED goes out.