1 General information
1.1 Correspondence table
75 W
12 V
6 A
24 V
3 A
48 V
The currents (In) shown are at rated output power.
1.2 Environmental specifications
Operating temperature:
-5 °C to +40 °C at 100 % charge.
-5 °C to +50 °C at 75 % charge.
-5 °C to +50 °C at 100 % charge for 75 W to 100 W.
Storage temperature: -25 to +85 °C.
Relative humidity: 20 to 95 %.
1.3 Electrical input and output specifications
1.3.1
Network input
single-phase voltage: 98 V to 264 V except 100-150 W: 195 V to 264 V.
-
frequency: 47 to 63 Hz.
-
class I.
-
neutral systems: TT, TN, IT.
-
Primary current @ 98 V
Primary current @ 195 V
Circuit breaker to be provided upstream: D curve
1.3.2
Output
Rated voltage
Floating voltage set at half-load and at 25 °C
Adjustment range (V) *
Limitation current
In power supply mode without battery exclusively. All use of the adjustment range in charger mode
with the battery will void the product's warranty.
100 W
150 W
8 A
12 A
4 A
6 A
2 A
3 A
75 W
100 W
150 W
1 A
-
0.5 A
0.75 A
200 W
300 W
16 A
24 A
8 A
12 A
4 A
6 A
200 W
300 W
-
3 A
4 A
1 A
1.5 A
2 A
12 V
13.6 V
±0.5 %
12-14 V
28
400 W
600 W
32 A
48 A
16 A
24 A
8 A
12 A
400 W
600 W
6 A
8 A
3 A
4 A
24 V
27.2 V
54.4 V
±0.5 %
23-29 V
In
48 V
±0.5 %
46-58 V