Vimar by-me Eikon 20525 Manual De Instrucciones página 4

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
Eikon
Arké
Idea
20525
19525
16965
Two simple push buttons and actuator with 8 A change-over relay output, to
be completed with interchangeable 1 or - 2 module buttons.
Device to be used as a double or single push button, depending on the button. The push button can be
configured independently from the relay too. The push button can only be pressed at the bottom.
CHARACTERISTICS.
• Rated supply voltage: BUS 29 V
• Input: 10 mA
• Changeover relay output
• Controllable loads at 120-230 V~ (contact NO):
- resistive loads:
8 A (20.000 cycles)
- incandescent lamps: 8 A (20.000 cycles)
- fluorescent lamps and energy saving lamps: 1 A (20.000 cycles)
- electronic transformers: 4 A (20.000 cycles)
- ferromagnetic transformers: 8 A (20.000 cycles)
• Controllable loads at 120-230 V~ (contacts NO and NC):
- motors cos ø 0.6: 3,5 A (100.000 cycles)
• Button: double or single
• Terminals: TP BUS, relay contacts (C, NC, NO)
• Possible functions:
- state reversal (step-by-step)
- button
- control ON only
- control OFF only
- scenario activation.
CONFIGURATION.
FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE THE By-me SYSTEM
INSTRUCTIONS MANUAL ATTACHED TO THE CONTROL UNIT.
Configuration must be done with the device without the key to be able to press the central configura-
tion button.
• Functional blocks: 3 (2 buttons, 1 relay), each functional block can belong to at most 4 groups.
• Selecting the functional block (configuration): during group creation, when the control unit requires
pressing the device button:
- press the central button;
- within 3 s, press the right-hand button to select the right functional block or the left-hand button to
select the left functional block; the red LED will light up. If neither button is pressed within approxi-
mately 3 s the red LED will light up; in this case, the selected functional block is the third one, the
one for the actuator;
- with the red LED on, the control unit will configure the functional block; at the end of this operation
the red LED will go out.
When the device is not configured, the actuator is controlled by the left-hand button and can already
be used.
PARAMETERS.
• For the functional blocks related to the two buttons it is possible to set the operating mode:
- simple button (ON when pressed, OFF when released);
- ON/OFF button (step-by-step);
- button ON only;
- button OFF only;
- scenario control.
• LED parameters:
- LED off;
- LED with normal operation (on if the associated actuator is ON);
- LED with reverse operation;
- LED always on for location in the dark.
- central LED with normal operation (on if the associated actuator is ON);
- central LED with reverse operation;
- central LED always on for location in the dark.
If the functional block belongs to more than one group, the "LED with normal operation" and "LED
with reverse operation" parameters are not available. In these cases the control is confirmed by a
LED status change for 3 s.
If a double key is used, it is necessary to set the central LED behaviour to make the status visible.
In this case, configure the left-hand button only.
• Functional block 3, related to the relay (see figure 1):
- one- or two-position stable operation;
- on delay and off delay: a value between 0 and 200 gives the time in seconds, a value between 201
and 250 gives the time in minutes (for example 201 = 1 minute, 202 = 2 minutes, etc.);
Monostable operation.
On delay: delay in closing the NO contact of the relay from receiving the close command.
Off delay: time for which the relay has the NO contact closed.
Bistable operation.
On delay: delay in closing the NO contact of the relay from receiving the ON command.
Off delay: delay in opening the NO contact of the relay from receiving the OFF command.
Viale Vicenza, 14 - 36063 Marostica VI - Italy
Tel. +39 0424 488 600 - Fax (Italia) +39 0424 488 188
Fax (Export) +39 0424 488 709
www.vimar.com
Plana
14525
FRONT VIEW.
A
Eikon
Arké
B
A
Idea
Plana
B
Caption:
A: configuration button - B: led
Note.
If a group is created with a number of relays in one-position stable mode, set for all the same on and
off delays and do not insert any other types of actuator in the same group; in this way, it is possible to
have the status of the one-position stable relay indicated on the control button. For special require-
ments it is possible to use the group depth (for example to switch on two-position stable relays or
dimmers with a single button).
• Default parameters: the buttons are set as ON/OFF push-buttons (step step) and LED in normal
operation.
FIGURE 1.
ON delay
ON delay
ON
Control
ON
ON delay
OFF delay
Control
Control
ON
OFF
SCENARIOS.
Each simple button can be dedicated to activating one scenario. The actuator can belong to up to 4
different scenarios and, for each scenario, save the status to retrieve when activating the scenario.
INSTALLATION RULES.
Installation should be carried out observing current installation regulations for electrical systems in the
country where the products are installed.
The feeding circuit of the relay output must be protected against overloads by a device, fuse or automatic
circuit breaker, with rated current not higher than 10 A. For further instructions, please see the manual
attached to the control panel.
CONFORMITY.
LV directive
EMC directive
Standard EN 50428
BACK VIEW.
A
B
A
NO
NC
terminals
TP bus
C
B
MONOSTABLE
OFF
BISTABLE
loading

Este manual también es adecuado para:

By-me arké 19525By-me idea 16965By-me plana 14525