Remote; Defrost Selection; Test Mode; Load Defaults - Air Energy AE-Ti Manual De Instalación Y Operación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3.
The maintain temperature delay is used when
MAINTAIN TEMP is connected. This feature
allows for a time delay before the pump is turned
on. To select Maintain Temperature Delay, use the
Up or Down button to scroll through to display
MAINTAIN TEMP DELAY . Press the MENU
button. The 00:30 HRS (default time) appears,
use the Up or Down button to scroll to display
the desired time delay, press the MENU button
to select. Press POOL or SPA to exit the Service
Setup mode.
7.3.3

Remote

Refer to Section 4.5.2.3, Configure the Control
Panel.
7.3.4

Defrost Selection

1.
Make sure the control is in the OFF mode.
2.
To enter the Service Setup mode, press and hold
the MENU, POOL and SPA button for 5 seconds.
NOTE The display will revert back to OFF after one
minute since the last key press.
3.
This feature allows for defrost mode using air
or hot gas. To select Defrost Selection, use the
Up or Down button to scroll through to display
DEFROST . Press the MENU button. The AIR
DEFROST (default mode) appears, use the Up
or Down button to scroll to display the desired
defrost option, press the MENU button to select.
Press POOL or SPA to exit the Service Setup
mode.
7.3.5

Test Mode

1.
Make sure the control is in the OFF mode.
2.
To enter the Service Setup mode, press and hold
the MENU, POOL and SPA button for 5 seconds.
NOTE The display will revert back to OFF after one
minute since the last key press.
3.
If enabled, this feature reduces delay settings by a
factor of 20. To select Test Mode, use the Up or
Down button to scroll through to display TEST
MODE . Press the MENU button. The DISABLE
(default mode) appears, use the Up or Down
button to scroll to display the desired test mode,
press the MENU button to select. Press POOL or
SPA to exit the Service Setup mode.
CAUTION
Disable TEST MODE after use. Failure to
disable TEST MODE after use will allow the
heat pump to bypass the built-in delays, which
could lead to equipment damage
NOTE The TEST MODE resets to DISABLE (default)
on every power-up.
7.3.6

Load Defaults

1.
Make sure the control is in the OFF mode.
2.
To enter the Service Setup mode, press and hold
the MENU, POOL and SPA button for 5 seconds.
NOTE The display will revert back to OFF after one
minute since the last key press.
3.
This feature allows for original factory settings
to be restored. To select Load Defaults, use the
Up or Down button to scroll through to display
LOAD DEFAULTS . Press the MENU button. The
NO (default mode) appears, use the Up or Down
button to scroll to display the desired option, press
the MENU button to select. Press POOL or SPA
to exit the Service Setup mode.
NOTE The LOAD DEFAULTS resets to NO (default)
after execution.
7.3.7

Coil Temperature Calibration

1.
Make sure the control is in the OFF mode.
2.
To enter the Service Setup mode, press and hold
the MENU, POOL and SPA button for 5 seconds.
NOTE The display will revert back to OFF after one
minute since the last key press.
3.
This feature adjusts the temperature reading in
the heat pump coil. To select Coil Temperature
Calibration, use the Up or Down button to scroll
through to display COIL TEMP CAL . Press the
MENU button. The 0°F (default mode) appears,
use the Up or Down button to scroll to display the
desired temperature adjustment, press the MENU
button to select. Press POOL or SPA to exit the
Service Setup mode.