Technical Data - Burkert 2510 Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Fluid Control Systems
Type 2510 / 2511
AS-Interface
Operating instructions
ENGLISH
To ensure that the unit functions correctly and will have a long
service life, please comply with the information in these Ope-
rating Instructions, as well as the application conditions and
the permissible data which are specified in the data sheets for the
solenoid valves used, as well as for the Type 2510/2511 AS interface
device socket.
• When planning the application of the unit, and during its operation,
observe the general technical rules!
• Work on the unit should only be carried out by specialists using the
correct tools!
• Take adequate measures to prevent unintentional operation or
impermissible impairment!
• Always switch off the supply voltage before working on the unit!
• If these instructions are disregarded or if unauthorised work is carried
out on the unit, no liability will be accepted from our side, and the
guarantee on the device and its accessories will become invalid!
The Type 2510/2511 AS Interface device socket is used to
control DC coils with performance ≤ 5 W, without an external
power supply.
• Watchdog function; NOTE: If no data traffic takes place, the output will
be reset after 50 - 100 ms.
• Connection of 2 sensors to the M12 socket (device socket with
feedback inputs).
Always switch off all voltages to the 2510/2511 AS Interface
device socket before carrying out work on it!
INSTALLATION / PUTTING INTO SERVICE
• Connect the round cable (2x 0.75 - 1.5 mm
connection diagram (Figure 3):
- Strip back the cable cover over approx. 15 mm
- Push on the coupling ring (1), the clamping sleeve (2) and the
seal (3)
- Fit the splice ring (4); ATTENTION: Polarity: 1 = Bus+ 2 = Bus-

TECHNICAL DATA

Operating voltage according to specification 29.5..31.6 VDC
Current consumption without valve and sensors 7 mA
Current consumption total max. 280 mA
Bus connection
AS Interface connection
QUICKON technology, PG11
Cable diameter
Round cable 2 x 0.75 - 1.5 mm
Addressability
min. 15 addresses
Output
Switching capacity / Voltage
max. 5 W / 24 V ± 10%
Current
max. 205 mA, short-circuit proof
Watchdog function
integrated
Device socket Type 2510 for plug pins (DIN 43650 Form C)
Device socket Type 2511 for plug pins (DIN 43650 Form A)
Inputs
Input switching
PNP
Sensor supply
via AS Interface
Sensor supply voltage
1)
24 V ± 10%
Max. admissible current
1)
max. 60 mA, short-circuit proof
≥ 10 V
1)
Switching level "1" signal
≤ 6,5 mA
Limitation of the input current
1)
≤ 1,5 mA
Input current "0" signal
1)
1)
For device sockets with feedback inputs
DEAR CUSTOMER
Congratulations on your purchase of this Bürkert unit. For your own
safety, please read carefully through these operating instructions
before installing the unit. Your local Bürkert branch will be pleased to
answer any questions you may have.
Figure 1: Type 2510/2511 AS interface device socket, plan view
We reserve the right to make technical changes without notice
© © © © © Bürkert Werke GmbH Co. All rights reserved
- Cut the wire ends flush
- Tighten the screw fitting
• Insert the cheesehead screw through the housing socket
• Push the flat seal onto the terminal pins of the solenoid valve
• Insert the device socket
• Secure the device socket using the cheesehead screw (max.
tightening torque 1 Nm)
ATTENTION! When screwing down the device socket, ensure that the
seal is properly seated!
PROGRAMMING DATA
I/O configuration
ID code
Preset address
Configuration of the data bits
D3
D2
IN 1
1)
IN 2
1)
DEVICE SOCKET WITH FEEDBACK INPUTS
• Via the M12 socket, 2 sensors can be connected using a
Y-distributor (see Fig. 2)
Type
2510
2
) as shown in the
2510
2511
2511
Table 1: Ordering data
Status displays
Switch status
LED off/on
Bus
LED off / on
LED blinking
2
Inputs
1)
LED off/on
Housing
Insulation / Material
Dimensions
Fixation Type 2510
Fixation Type 2511
Operational temperature
1 2-pole QUICKON connection
2 M12 socket, inputs
1)
3 LED input 2 (yellow)
1)
on
switched
off
not switched
1)
4 LED input 1 (yellow)
on
switched
off
not switched
5 Bus LED (yellow)
off
Power off
on
OK
blinking
Slave address = 0
6 Status display LED output (green)
on
switched
off
not switched
7 Fixing screw
B hex (1 output, 2 inputs)
F hex (for configuration, see below)
0
D1
D0
-
OUT
Feedback Inputs
Order No.
no
139 202 G
yes
140 069 J
no
140 071 C
yes
140 070 P
green LED
not switched / switched
yellow LED
Power off / OK
Slave address = 0
yellow LED
not switched / switched
IP 65 / PA
32 x 32 x 65 mm
M2.5 x 35 cheesehead screw
M3 x 35 cheesehead screw
0 to +50 °C
1
+ 24 V sensor supply
2
Sensor input 2
3
GND
4
Sensor input 1
Figure 2: Pin allocation of the M12 socket
3
2
1
Figure 3: QUICKON Connection of the device socket
BÜRKERT GERMANY
Chr.-Bürkert-Straße 13-17
Berlin
74653 Ingelfingen
Dortmund
Ph: (0 79 40) 10-0
Dresden
Fax (0 79 40) 10-204
Frankfurt
Hannover
München
Stuttgart
BÜRKERT INTERNATIONAL
A
Ph.
(01) 8 94 13 33
AUS
Ph.
(02) 96 74 61 66
B
Ph.
(03) 3 25 89 00
CDN
Ph.
(9 05) 8 47 55 66
CH
Ph.
(0 41) 7 85 66 66
CZ
Ph.
(06 41) 22 61 80
DK
Ph.
(0 44) 50 75 00
E
Ph.
(93) 3 71 08 58
ET
Ph.
(0 40) 54 27 38
F
Ph.
(01) 48 10 31 10
GB
Ph.
(0 14 53) 73 13 53
HKG
Ph.
24 80 12 02
I
Ph.
(02) 9 52 01 59
J
Ph.
(03) 32 47 34 11
KOR
Ph.
(02) 34 62 55 92
N
Ph.
(0 63) 84 44 10
MAL
Ph.
(04) 6 57 66 49
NL
Ph.
(0 34) 6 59 53 11
NZ
Ph.
(09) 5 70 25 39
P
Ph.
(01) 4 42 26 08
PL
Ph.
(0 22) 6 27 47 20
RC
Ph.
(02) 27 58 31 99
S
Ph.
(0 40) 66 45 100
SF
Ph.
(09) 5 49 70 600
SGP
Ph.
3 83 26 12
TR
Ph.
(02 32) 4 59 53 95
USA
Ph.
(9 49) 2 23 31 00
ZA
Ph.
(0 11) 3 97 29 00
Operating Instructions No. 801 799 01/99/02
4
Ph: (0 30) 67 97 17 - 0
Ph: (0 23 73) 96 81 - 0
Ph: (03 59 52) 36 30 - 0
Ph: (0 61 03) 94 14 - 0
Ph: (05 11) 9 02 76 - 0
Ph: (0 89) 82 92 28 - 0
Ph: (07 11) 4 51 10 - 0
Fax
(01) 8 94 13 00
Fax
(02) 96 74 61 67
Fax
(03) 3 25 61 61
Fax
(9 05) 8 47 90 06
Fax
(0 41) 7 85 66 33
Fax
(06 41) 22 61 81
Fax
(0 44) 50 75 75
Fax
(93) 3 71 77 44
Fax
(0 40) 54 41 65
Fax
(01) 48 91 90 93
Fax
(0 14 53) 73 13 43
Fax
24 18 19 45
Fax
(02) 9 52 90 33
Fax
(03) 32 47 34 72
Fax
(02) 34 62 55 94
Fax
(0 63) 84 44 55
Fax
(04) 6 57 21 06
Fax
(0 34) 6 56 37 17
Fax
(09) 5 70 25 73
Fax
(01) 4 42 28 08
Fax
(0 22) 6 27 47 20
Fax
(02) 27 58 24 99
Fax
(08) 7 24 60 22
Fax
(09) 5 03 12 75
Fax
3 83 26 11
Fax
(02 32) 4 59 76 94
Fax
(9 49) 2 23 31 98
Fax
(0 11) 3 97 44 28
Tabla de contenido
loading

Este manual también es adecuado para:

2511

Tabla de contenido