WARNINGS:
• It is important that users of this tester read, understand, and follow all warnings,
cautions, safety information, and instructions in this manual before operating or
servicing this tester. Failure to follow instructions could result in death or serious injury.
• Risk of electric shock and burn. Contact with live circuits could result in death or
serious injury.
• Use caution with voltages above 30V AC as a shock hazard may exist.
• A blinking or steady red glow and an audible beep indicate voltage present. If no
indication, voltage could still be present.
• Before and after each use, verify operation by testing a known working circuit that
is within the rating of this unit.
• Never assume neutral or ground wires are de-energized.
• The tester WILL NOT detect voltage if:
• the wire is shielded.
• the operator is not grounded or is otherwise isolated from an effective earth ground.
• the voltage is DC.
• The tester MAY NOT detect voltage if:
• the user is not holding the tester.
• the user is insulated from the tester with a glove or other materials.
• the wire is partially buried or in a grounded metal conduit.
• the tester is at a distance from the voltage source.
• the fi eld created by the voltage source is being blocked, dampened, or
otherwise interfered with.
• the frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
• the tester is outside of operation conditions (listed in Specifi cations section).
• Operation may be affected by differences in socket design and insulation thickness
and type.
• In bright light conditions, the LED visual indicators will be less visible.
• Do not use if green LED is not illuminated.
• Do not use if tester appears damaged or if the tester is not operating properly. If in
doubt, replace the tester.
• Do not apply more than the rated voltage as marked on the tester (1000 volts AC).
• Detection above 50V is specifi ed under "normal" conditions as specifi ed below.
The tester may detect at a different threshold at different conditions, or may not
detect at all unless:
• The tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
• The user is holding the body of the tester with his or her bare hand.
• The user is standing on or connected to earth ground.
• The air humidity is nominal (50% relative humidity).
• The tester is held still.
• Always wear approved eye protection.
• Comply with local and national safety requirements.
• If this product is used in a manner not specifi ed by the manufacturer,
protection provided by the product may be affected.
CAUTION:
• Do not attempt to repair this tester. It contains no serviceable parts.
• Do not expose the product to extremes in temperature or high humidity.
SPECIFICATIONS:
VOLTAGE RANGE: 50-1000 Volts AC
TESTER TYPE: Non-Contact Voltage Detector
UL CERTIFICATION
E321008 3TMV
FREQUENCY RANGE: 50-500Hz
STANDARDS:
UL 61010-1 2nd edition
CAN/CSA C22.2 No. 61010-1-04
EN 61010-1 2nd edition
IEC 61010-1:2001 2nd edition
ISA-82.02.01 (IEC 61010-1 MOD)
CAT IV RATED
DOUBLE INSULATED
POWER ON INDICATOR AND
ILLUMINATOR:
Visual: High Intensity Green LED
POWER OFF & AUTO POWER OFF:
Visual: Power-On LED Turns OFF
Audible: Double Beeping Sound
LOW BATTERY INDICATORS:
Visual: Green LED Blinks
Audible: Series of Beeping Sounds
CAT
IV
VOLTAGE DETECTION INDICATORS:
Visual: High Intensity Red LED
Audible: Continuous Beeping Sound
OPERATING CONDITIONS:
Temperature: 32° to 104° F
(0° to 40° C)
Relative Humidity: <80%
Altitude: Up to 6,562 feet
(2,000 meters) maximum
Environment: Indoor Use
STORAGE CONDITIONS:
Temperature: 32° to 104° F
(0° to 40° C)
Relative Humidity: <80%
Altitude: Up to 6,562 feet
(2,000 meters) maximum
Environment: Indoor
POLLUTION DEGREE: 2
BATTERIES: Two AAA 1.5 volt or
IEC LR03 or NEDA 24A
PATENTS: US D583,266 S
DISPOSAL: DO NOT THROW
IN TRASH; PLEASE RECYCLE.