Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

V2 > 266V
I1 and I3 > 95A
The device resumes correct value readings when voltage and/or current get back into
the admitted ranges (V ≤ 253 and I ≤ 90A respectively).
CONFIGURATION ERROR
Every 30 seconds the software checks confi guration settings in some internal registries;
if an invalid datum is detected, the device is automatically reconfi gures until the error
disappears.
During these steps, the device does not measure any quantity and reads "CHIP Error"
Confi guration error
If the error warning stays on even after disconnecting and reconnecting the device from
the mains, the latter must be considered as faulty.

REFERENCE STANDARDS

Conformity with EU Directives:
2006/95/EEC (Low Voltage)
89/336/EEC amended by 92/31/EEC and 93/68/EEC (EMC)
is declared with reference to the following harmonized standards:
• Safety: EN 61010-1
• Electromagnetic compatibility: EN 61000-6-2 and EN 61000-6-4,
• Metering requirements: EN 62052-21 and EN 62053-23
- 42 -
User Manual - ANRET M-90A-BUS
Tabla de contenido
loading

Tabla de contenido