Soft Starter - Sulzer EC 531 Guia De Instalacion

Controlador de equipos
Ocultar thumbs Ver también para EC 531:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ACS 550
9902 Applic. macro
9802 Comm prot sel
1001 Ext1 commands
1103 Ref1 select
1604 Fault reset sel
5302 EFB station ID (Node address)
5303 EFB baud rate
5304 EFB parity
5305 EFB ctrl. profile
For PSTx the "Poll interval" in controller must be set to 0 second (as fast as possible) to avoid drive
trip, this as the PSTx have an internal (not adjustable) fieldbus timeout of 0.1 second, before drive
trips and stops the motor.
With this short timeout, only one corrupt Modbus message may trip the drive. Adjust drive setting
19.04 to the safety level required for your application.
PSTx
12.01 Com3 function
12.02 FB interface connector
12.03 Fieldbus control
12.04 Fieldbus address
12.09 FB baud rate*
12.10 FB parity
12.11 FB stop bits
12.12 Fieldbus DI 1
12.13 Fieldbus DI 2
12.14 Fieldbus DI 3
12.15 Fieldbus DI 4
12.16 Fieldbus DI 5
12.17 Fieldbus DI 6
12.18 Fieldbus DI 7
12.19 Fieldbus DI 8
12.20 Fieldbus DI 9
12.21 Fieldbus DI 10
12.22 Fieldbus AI 1
12.23 Fieldbus AI 2
12.24 Fieldbus AI 3
12.25 Fieldbus AI 4
12.26 Fieldbus AI 5
12.27 Fieldbus AI 6
12.28 Fieldbus AI 7
12.29 Fieldbus AI 8
ES
Variable speed drive
1 = ABB standard
1 = Std modbus
10 = Comm
8 = Comm
8 = Comm
If remote drive reset is enabled in EC 531
Unique slave ID corresponding to EC 531 setting
Same as EC 531
Same as EC 531
0 = ABB Drv Lim

Soft starter

Modbus RTU slave
Modbus RTU
Off if "Monitor" On if "Control ON/OFF" over fieldbus
Unique slave ID corresponding to EC 531 setting
Same as EC 531 limited to 9600 or 19200
Same as EC 531
Same as EC 531
Run status (default)
TOR status (default)
Line (default)
Phase sequence (default)
Start feedback (default)
Stop feedback (default)
Event group 0 status (default)
Event group 1 status (default)
Event group 2 status (default)
Event group 0 status (default)
Phase L1 current
Phase L2 current
Phase L3 current
Motor current
Mains frequency
Mains voltage
Apparent power
Active power
12
Tabla de contenido
loading

Tabla de contenido