KEB COMBIVERT F5 Manual De Instrucciones página 40

Unidad de potencia tamaño w
Ocultar thumbs Ver también para COMBIVERT F5:
Tabla de contenido
Anexo
Short Circuit rating and Branch Circuit Protection:
Following marking shall be provided:
All 480V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 kA rms Symmetrical Amperes, 240 Volts Maxi-
mum when Protected by Class ___ Fuses, rated ____ Amperes as specified in table I":
or when Protected by A Circuit Breaker Having an Interrupting rating Not Less than 100 kA rms Symmetrical Amperes,
480V maximum, rated ___ Amperes as specified in table I":
Table I Branch Circuit Protection of inverters F5 – W – housing:
a) UL 248 Fuses; Class RK5 as specified below
Inverter
28.F5
29.F5
30.F5
31.F5
32.F5
b) UL 489 Circuit Breaker
Inverter
28.F5
29.F5
30.F5
31.F5
32.F5
E - 40
Input
Voltage [V]
480 / 3ph
480 / 3ph
480 / 1x 3ph
480 / 2x 3ph
480 / 2x 3ph
480 / 2x 3ph
Input
Voltage [V]
480 / 3ph
480 / 3ph
480 / 1x 3ph
480 / 2x 3ph
480 / 2x 3ph
480 / 2x 3ph
UL 248 Fuse
class RK5,
max. [A]
400
500
600
2 x 315
2 x 350
2 x 400
UL 489 MCCB
máx. [A]
400
600
600
2 x 400
2 x 400
2 x 400
Siemens
Cat. No.
3VL400 / JG-frame
3VL400X / LG-frame
3VL400X / LG-frame
2x 3VL400 / JG-frame
2x 3VL400 / JG-frame
2x 3VL400 / JG-frame