The following registers are available with the energy meter firmware:
Registers
30527-30528
32043-32048
Totalizer #2 units
30003-30004
Temperature #2
30011-30012
The following registers contain the display units strings:
Registers
32007-32012
Volume flow units
32001-32006
Mass flow units
32025-32030
Temperature units
32019-32024
Pressure units
32031-32036
Density units
32013-32017
Energy flow units
Function codes 03 (read holding registers) and 04 (read input registers) are the only codes
supported for reading these registers, and function codes for writing holding registers are not
implemented. We recommend that the floating point and long integer registers be read in a
single operation with the number of registers being a multiple of two. If these data are read in
two separate operations, each reading a single 16-bit register, then the value will likely be invalid.
The floating point registers with values in display units are scaled to the same units as are
displayed, but are instantaneous values that are not smoothed. If display smoothing is enabled
(non-zero value entered in the Display TC item in the Display Menu), then the register values
will not agree exactly with the displayed values.
94
Table 4 Register Definitions
Variable
Data type
Totalizer #2
unsigned long
Energy flow
Variable
Data type
Units
display
units*
string
—
display
float
units*
display
float
units*
Units
string
—
string
—
string
—
string
—
string
—
string
—
Function
Addresses
code
03, 04
526-527
03, 04
2042-2047
03, 04
2-3
03, 04
10-11
Function
Addresses
code
03, 04
2006-2011
03, 04
2000-2005
03, 04
2024-2029
03, 04
2018-2023
03, 04
2030-2035
03, 04
2012-2017
IM-P339-06 MI Issue 2