Installation and operating instructions
GB
Ecocirc
Operating LEDs /
Flashing light
Off
1 x short + 1 x long
3 x short + 1 x long
5 x short + 1 x long
Proceed as follows for other faults:
Fault
Pump is making
loud noises
Note regarding temperatures that are too high:
In order to protect the electronics from temperatures that are too high, the
pump's power, and thus the flow of water that is too hot, is automatically
reduced. The temperature is measured directly at the electronics. When the
temperature of the electronics is between 105 °C and 115 °C, the pump power
is continuously lowered toward minimum power from the power specified on the
power selector switch. The pump automatically stops completely at 15 °C and
automatically restarts at 115 °C, when the electronics have cooled down, begin-
ning at minimum power. As cooling down proceeds further, the power continues
to be adjusted, up to the value that is set.
16
vario E4 and E6 heating pumps
®
Cause
- Pump is not or is
incorrectly connected
- Power failure
- Voltage too low
- Temperature too high
- Pump blocked
Cause
- Not thoroughly bled
- Foreign objects in pump - See section 8 "Maintenance/
- Bearing is worn
Solution
- Check connection
- Check mains + fuse
- Check mains voltage
- Pump restarts
automatically
(see the notes below)
- Determine max. system
temperature
- See section 8 "Maintenance/
Disassembly"
Solution
- See section 7. "Getting
started"
Disassembly"
- Replace pump
www.laing.de