1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive
atmospheres.
The luminaires must not be operated in Zone 0
and Zone 20.
The tecnical data indicated on the luminaires
are to be observed.
Changes of the design and modifications to the
luminaires are not permitted.
The luminaires shall be operated as intended
and only in undamaged and perfectconditions.
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
ouse-Hinds, S.A.
Only genuine Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A. spare
ouse-Hinds, S.A.
parts may be used for replacement.
Repairs that affect the explosion protection, may
only be carried out by
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Cr
ouse-Hinds, S.A. or a qualified
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
"electrician" and will subsequenctly have to be
cheked by an "expert".
Do not keep these operating instructions inside
the luminaire during opertion.
The national safety rules and regulations for
prevention of accidents and the following
safety instructions which are marked with an
(
) in theses operting instructions, will have
to be observed.
2.Conformity with standards
This explosion protected luminaires meets the
requeriments of IEC/EN 60079-1, IEC/EN 60079-7,
IEC/EN 61241-1 and EN60598. It also complies with
the EC Directives for "Apparatus and protective
systems for use in explosive atmospheres"
(94/9/EC) and "Electromagnetic compatibility"
(89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use hazardous areas,
in Zone 1 and 2 acc. to IEC60079-10 Zones 21 and 22
acc. IEC 61241-10.
3. Technical data
Application
II2D
Class I:
Exd / de IIC T6
Class II:
Ex tD A21 IP 67 T85ºC
Certificates:
LOM 02 ATEX2012X
Others, contact us
Category of application:
II2G EExd / de IIC T6
IP67 T85ºC
Serie of types:
See Table 1
Lamps to be use
2)
:
Induction lamp
QL (PHILIPS)
Approval of the production
ATEX Quality assurance: LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
Temperature of use:
-20
C a + 55
o
Rated voltage standard See Table 1
Material of enclosure:
Metal aloy aluminium
without Cu,painted
polyester grey.
Notes:
2) There are no limitation for these EVQ luminaries.
The symbol "X" is retened to the EVI luminaries, that they have the lamp certificate of -CE examination type.
Material of glass
Storage temperature in original
Packing
Terminals capacity:
Entries of cables:
Dimensions:
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have to be
observed!
¡Transport and storage of the luminaire is
permitted in original packaging only!
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions!
¡Numer maximum to lamps for MCB, see
table 2
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the
glass-collar and covers are completly
threaded on the luminaire enclosure!
See figures 1 and 2
Dimensions for mounting:
Accesories for mounting:
See Cooper Cr
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cable entries
¡Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type
and dimensions of the main conection cable,
following their manufacturer instructions!
¡The cable entries devices has to be the same
protection mode than the enclosure where they
are mounting!
¡Unused cable entries have to be closed by a
correspondante certified blanking plug.
If the original blanking plugs are used , these
must be tightened with 15 Nm torque!
Main conection:
QL Lamps
¡Only must be side mounting PHILIPS lamps
QL system for induction.
See indications in the general label of the
luminaire!
- HF Generator
-Antenna and
2)
-Lamp bulb
adequated for instalation power.!
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions and
others applicable regulations!
Only carry out inslation measurement wit Megget at
500V DC between earth and, active conductors
(F and N) every one of separated.
-isolement min. 2 MΩ
Non testing between F and N, because it's
C
o
possible damage the HF generetor. It is
recommended carry out the test disconecting the
N of the installation in order to avoid external
influences.
Borosilicate
-40
o
C a + 60
o
C
See wiring diagram
See Table 1
See Table 3
See Table 3
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. catalogue
ouse-Hinds, S.A.
See wiring diagram.
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive atmospheres,
as well as the general rules of engineering!
Servicing
¡The responsable of the safe use of these
apparatus is the property!
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas and blanking plugs for their firm fix.
Lamp replacement in acc. with the
manufacturer instructions.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to
ensure it protection in front of the corrosion,
water ingrees and seize-up problems. Cleaning
rest of greasse and corrosion no using sharp
metallic devices who can damage the surface of
the joint, and greasing they using apropiate
greasse thermically and chemically stable, like
e.g.: Molikote
BR2 plus.
¡When the housing need to be repeinted, pay
attention that the flameproof joints rest without
Traks of coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires
have to be disconnected from the main
conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of repairing have to be
made by "qualified" personnel!
¡The reparation of the sealed part between the
collarand the glass have to be done by
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A..
ouse-Hinds, S.A.
The users are not authorized to repair this sealed
part!
¡All reparations have to be done without voltage!
Pay attention to the length and thincknesr of
the screws when it was necessary replace the
autenc. See figure 3.
Pay attention, when it was necessary replace
the generetor of the 85W luminaire it will be
necessary send the apparatus to the
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. factory because the HF
ouse-Hinds, S.A.
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
generator is sealed in the housing of the luminaire.
For repair electrical equipments in protection mode is
suggested follow the instructions indicated
in IEC 79-19.
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
¡Only use genuine Cooper Cr
Cooper Cr
spare parts!
Subject to alteration or supplement of this product
without any advertisement before.
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
6