1. Safety instructions

Installation and electrical connections of
equipments and control stations may only
be carried out by skilled electricians and
instructed personnel in accordance with
60079-14 and the respective national
legislation on electrical equipment for
explosive atmospheres.
This explosion protected equipments and
distributions must not be operated in
Zone 0 or 20 hazardous areas.
The requirements of EN 61241-0, -1 and
60079-0 regarding excessive dust deposits
and temperature must be considered by
the user.
The technical data indicated in point 3
as well as those indicated in the technical
documentation
supplied
equipment, must be observed.
It is necessary to ensure that the power
dissipation of equipment is not exceeded
(see technical documents supplied with
the equipment). The temperature class
and explosion group stated on the
equipment shall be observed. To ensure
adherence to the temperature class stated
on the type label of the equipment, the
permissible ambient temperature, the
rated terminal cross section and the self
heating of the equipment mainly due to
the power dissipation shall be taken into
account (test criterion for the self heating
is an overload of 10%).
Modifications or design changes to
equipment and distributions that affect
the
explosion
protection
permitted.
They shall be used for their intended
purpose and shall be in a perfect and
clean state.
Only original COOPER Crouse-Hinds
parts may be used as replacements and
for repairs.
Repairs
that
affect
the
protection may only be carried out by
COOPER Crouse-Hinds or by a qualified
electrician in compliance with the res-
pective national regulations.
Prior to being put into operation, the EFS
control stations shall be checked in
accordance with the instructions as per
section 6.
The operator is required to ensure that
the overall current of a distribution with
bus bar systems does not exceed the values
stated in the technical data of the
equipment.
Distributions mounted on a floor frame
shall be safeguarded against falling over.
Before initial operation, any foreign
matter shall be removed from the EFS
control stations, do not keep this
operation instructions not technical
documentation inside the equipment
during its operation.
The national safety rules and regulations
for the prevention of accidents, as well as
Cooper Crouse-Hinds, S.A.
7
Explosion protected switchgear equipments and control stations. Serie: EFS

2. Conformity with standards

This equipment is conform to the standards
specified in the EC-Declaration of conformity. It
has been designed, manufactured and tested
according to the state of the art and to
DIN EN ISO 9001, 94/9 EC: Equipment and

3. Technical data

Apparatus marking acc. to 94/9/EG directive:
II 2 G
II 2 D
EC-type examination certificate:
Rated voltage:
Ratet current:
Terminals capacity:
Perm. ambient temperature:
The actual permissible Ta range for each equipment is stated on the type label of the enclosures.
Perm. storage temperature in original packing:
with
the
Degree of protection EN/IEC 60529:
Insulation class acc. to EN/IEC 60598:
Enclosure material (standard version):
Enclosure surface finish:
Colour of enclosure (standard version):
Wall or standing framework:
Dimensions of equipments:
Cable entries:
3
Table
are
not
Type
EFS A
EFS A/A
EFS A/A/A
explosion
EFS 250
EFS 325
EFS 72
Use or Content
Switches
1 push-button or signal lamp
2 LS push-buttons
3 push-buttons or signal lamps
For breakers
the 1, 2, 3, ó 4 poles
for Guard
With sight glass measuring instruments
or electronic devices
P disipado < 25W
protective systems intended for use in potentially
explosive atmospheres. The equipment fulfill
further requirements, such as the EC directive
on electromagnetic compatibility (2004/108/EC).
Ex d IIC T6 Gb
Ex t IIIC T85ºC Db
LOM 03 ATEX2034
See table
See table
2
2 x 2,5mm
internal apparatus according rest
-20ºC up to +55ºC
-40°C to +60ºC
IP 67
I
Aluminium alloy casting (Cu free)
Plastic powder coating
RAL 7032, cover RAL 7016
Iron U-profile painted or galvanized acc. to
application
See table 2 or technical documentation
supplied with products.
See table 2 or technical documentation
supplied with products.
Nominal voltage
690V
690V
415V
6900V
690V
Rated
25A
63A
60A
25A
5A