14. Storage volume/combined storage/provision
Please observe the national regulations depending on the type class of the cabinet.
Models TRG.205.xxx, G90.xxx.xxx
The entire volume of the pressurised gas cylinders stored may not exceed 210l + 10l for a scavenging gas cylinder.
15. Marking
All models are labelled in compliance with the requirements of EN 14470-1 and DIN 12925-1 and DIN 12925-2
(EN 14470 Part 2 after its publication) (in the case of TRG- and G90-models).
16. Opening the cabinet after a fire
Warning: the cabinets may only be opened following a fire after a period of 6 times the duration of the fire. Depending
on the duration of the fire, an ignitable vapour-air mixture may have formed. Before opening the cabinets, remove all
ignition sources within a radius of at least 10 m around the cabinets. Only open the doors with the utmost care. Only
use spark-free tools.
17. Disposal
All models have been constructed so that they may be disposed of in dismantled form, sorted according to materials.
The cabinets contain no materials which need to be disposed of as special waste.
18. Safety check
Being a safety equipment the cabinets should be checked once a year as minimum for faultless function as per manu-
facturer's specification.
Please refer to the test plate on the outside of the door for the next inspection date.
This annual inspection can only be performed with the requisite care and to secure your warranty claims in case of fire
by an authorised asecos employee (refer also to Splus Agreement in our general catalogue).
We also recommend that you carry out a functional check on a daily and monthly basis.
The daily inspection should also extend to the collecting sumps (any leakage must be mopped up and removed
immediately).
The perfect function of the door(s), and the correct fit and state of the fire protection seals should be inspected on a
monthly basis. (In case of damage, please contact your specialised dealer to have the cabinet repaired with original
parts.)
Many other products for the safe handling of all kinds of hazardous materials can be found in our general cata-
logue available free of charge by phoning +44 (0) 1952 814 202.
In the case of faults and complaints with regard to our products during and after the warranty period and to
request safety inspections please contact your specialised dealer mentioned on the back of your instruction
manual.
17

Capítulos

Tabla de contenido
loading

Tabla de contenido