Installation
Instructions
INSTALLATION--GAS CONNECTIONS
r_
PROVIDE ADEQUATE
GAS SUPPLY
This cooktop
is designed to operate on natural
gas at 5" of water column manifold
pressure and
7" of water column (W.C.) supply pressure. It is
shipped from the factory set for natural gas. The
convertible
pressure regulator
supplied with the
unit must be connected
in series with the manifold
of the cooktop and must remain in series with the
supply line regardless of whether
natural or L.P.
gas is being used. FOR PROPER OPERATION, THE
HAXIHUH INLET PRESSURETO THE REGULATOR
HUST BE NO HaRE THAN 14" OF WATER COLUHN
PRESSURE.For checking the regulator, the inlet
pressure must be at least 1" W.C.. (or 3.4 KPA)
greater than the regulator
output setting. If
the regulator
is set for 5" W.C. of water column
pressure, the inlet pressure must be at least 6" W.C.
If the regulator
is set for 10" W.C., the inlet pressure
must be at least 11" W.C.. The gas supply line to
the cooktop should be 1/2" or 3/4" pipe.
J_
INSTALL REGULATOR
NEVER REUSE OLD CONNECTORS WHEN
INSTALLING THIS COOKTOP.
AWARNING:
Never reuse old flexible
connectors.
The use of old flexible connectors
can cause gas leaks and personal injury. Always
use new flexible connectors
when installing a gas
appliance.
Screw a section of pipe onto
the inlet end of the pressure
regulator
and install the
coupling.
Pressure __-]
Regulator
'_
Coupling
_
t_
To reduce the likelihood of gas leaks, apply teflon
tape or a thread compound
approved
for use with
LP or Natural gases to all threaded
connections.
r3] INSTALL REGULATOR
ONTO
BURNER
BOX BOTTOM
Screw the regulator
onto the burner
box bottom
pipe
connection.
Hake
sure the top of
the regulator
is
facing towards
the
cabinet front, easily
accessible through
the cabinet doors.
The regulator
may
also be installed
prior to inserting
Pressure
_1
Regulotor-=---_l
Coupling
l
LI
:\
Ii
Electrical
II
Outlet 12"
I
Below
Countertop
the cooktop
into the cutout if extreme caution is
used to ensure the regulator
connection
is not
compromised.
r_
COMPLETE CONNECTION
WITH A
COUPLING
Complete the
connection
between
the regulator
pipe
coupling
and
the shut-off valve.
Pressure
Regulator
Coupling
Shut-Off _7
Valve
I
II
II Electrical
I Outlet 12"
I
Below
Countertop