Initial configuration
The first time the unit receives the power supply, it will enter into ASSISTANT mode. The lower display will show the
message In1 flashing with 0.
Step 1: Cold regulation type
1
AUX
Select the most suitable option based on the type of
installation to be carried out and press SET. The available
options are shown in the table on the following page.
Step 2: Moisture regulation type
2
AUX
Select the most suitable option based on the type of
installation to be carried out and press SET. The available
options are shown in the table on the following page.
The configuration wizard will not reactivate. To reactivate it, activate the Stand-By mode (by pressing the m
key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up
permanently) and press keys N, Q and SET in sequence.
If this is not the first time you run the wizard, after completing the last step the display will show the message dFp
(default parameters). You may choose between two options:
0: Only change the parameters which affect the wizard. The other parameters will remain the same.
1: All parameters return to their factory setting except those which have been modified by the wizard.
Step 3: Temperature Set Point
3
AUX
Use keys N and Q to enter the desired Set Point value
and press SET.
Step 4: Moisture Set Point
4
AUX
Use keys N and Q to enter the desired moisture Set Point
(SPH) value and press SET.
17 17
1662H411 Ed.01