Puls Dimension YR2.DIODE Manual De Instrucciones página 3

YR2.DIODE Decoupling Module Instruction Manual
Technical Data
Input
Output
Voltage drop
typ.
Peak current
Reverse current
max.
Ensure that the continuous output current does not exceed 25A. Check the
short-circuit current of power sources. And if the power source can deliver
more than 25A, use an appropriate fuse on the output.
Limited Warranty
Functional Diagram
+
V
1
IN
-
+
V
2
IN
-
Environment
Operational temperature
Storage temperature
Humidity
Vibration sinusoidal
Shock
Allowed output current versus
the ambient temperature
Ambient temperature is defined
2cm below the unit.
EMC
The device is suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.
This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
CE mark in conformance with EMC guideline 89/336/EEC and 93/68/EEC and low-voltage directive (LVD) 73/23/EWG.
Terminals and Connections
open
1.
Insert the wire
Physical Dimensions, Indicators and Cooling
Width
32mm / 1.26''
Height
124mm / 4.88''
Depth
102mm / 4.02''
Weight
290g / 0.64lb
Use DIN-rails according to EN 60715 or EN 50022
DIN-Rail
with a height of 7.5 or 15mm
Mounting
Input terminal on top and output terminals on the bottom.
Orientation
For other orientations consult factory.
Do not obstruct air flow! The unit is convection cooled.
Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient
temperature and full load:
40mm on top, 20mm on the bottom, 5mm on the left and
right side are recommended when loaded permanently
with full power. In case the adjacent device is a heat
source, 15mm clearance are recommended.
YR2.DIODE
DC 10-60V
2x10A or 1x20A
continuous
2x15A or 1x30A
for typ. 4 sec
0-20A
continuous
0-30A
for typ. 4 sec
0.9V
V
- V
IN
OUT
150A for 10ms
each input
2mA
each input
3 year
Typical input to output voltage drop
V
Drop
1,0V
+
0,9V
V
-
OUT
0,8V
0,7V
Chassis
0,6V
Ground
0,5V
0,4V
0,3V
0A
-40 to +70°C
De-rate above +60°C
-40 to +85° C
Storage, transport
5 to 95% RH
No condensation allowed
2g
IEC 60068-2-6
30g 6ms, 20g 11ms
IEC 60068-2-27
for 4s
30A
I
25A
OUT
continuous
20A
15A
10A
5A
Ambient Temperature
0A
-40°C -20°C 0°C
20°C 40°C 60°C 80°C
close
2.
Snap the lever
plus DIN-rail depth
Output C urrent
4A
8A 12A 16A 20A 24A 28A
Protection
Degree of protection
Class of protection
Degree of pollution
Penetration protection
Safety
Isolation voltage
Isolation resistance
PE resistance
Approvals
EMC Immunity
EMC Emission
Terminals
Type
Ferrules
Solid wire
Stranded wire
AWG
Stripping length
Pull-out force
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient
up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point.
Test circuitry for voltage drop curve
V
V
IN
YR2.DIODE
+
Power
Supply
IP 20
EN/IEC 60529
II
PE (Ground) connection required!
2
EN 50178, not conductive
>3.5mm
e.g. screws, small parts ...
500Vac
against housing
min. 5MOhm
against housing, 500Vdc
max. 0.1Ohm
Between housing and chassis ground terminal
See datasheet or markings on the unit
EN 61000-6-1, EN 61000-6-2
EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B
Inputs
Bi-stable, quick-connect spring clamp terminals
Allowed, but not required
2
0.5-6mm
2
0.5-4mm
AWG 20-10
10mm / 0.4inch
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (UL486E)
Air flow
Variable
Load
V
OUT
V
Output
2
0.5-6mm
2
0.5-4mm
AWG 20-10
loading