If the Aduro H1 is to be placed close to flammable material, such as a wooden floor or carpet, it must be
placed on a non-flammable base. The floor plate should extend for at least 30 cm in front of the Aduro H1,
and 15 cm on each side – measured from the combustion chamber opening.
The Aduro H1 must be installed on a floor with the adequate load-bearing
capacity. If the existing construction does not meet this requirement,
appropriate adaptation measures must be taken (e.g. a load-distributing plate).
2.2 Pipe connection
Aduro H1 leaves the factory with the flue outlet mounted on the top. If you require the flue outlet on the back,
remove the round circle from the rear cover at the upper rear of the stove and then exchange the exhaust
connector (located on the top outlet above the stove) with the cover plate (that covers the rear outlet). The
top outlet is finished with the plate that lies in the ash drawer. A flue pipe with an internal diameter of 150 mm
should be used for Aduro stoves.
Aduro H1 is tested and approved for use with an uninsulated fluepipe of minimum 100 cm.
2.3 Connection to a brick chimney
If the stove is being connected to a brick chimney, the rear outlet should be used, or a curved flue pipe via
the top outlet. After measurement, a hole is made in the chimney in which the pipe sleeve is placed and
fireplace mortar is used to seal it in place. The stove is placed in position and the flue pipe is put in place. A
50