M04 - INTEGR TION
P04.01
Integration mode
P04.02
Power integration time
P04.03
Current integration time
P04.01 - Selection of average reading calculation method:
Fixed = Readings are integrated for the set time. Every time the integration time elapses, the verage value is updated with the result of the last integration.
Shift = The instantaneous values are integrated for a period f time equal to 1/15th of the set time. Every time this interval elapses, the oldest value is replaced
with the new one just calculated. The average value is updated every 1/15th of the time set, considering a time-sliding window that groups the last 15 calculated
values, with a total length equal to integration time setting.
P04.02 = verage readings integration time, used for active, reactive and apparent power.
P04.03 = Readings integration time, used for currents.
M05 - HOUR COUNTER
P05.01
Hour counter enable
P05.02
Partial hour counter enable
P05.03
Reference measurement
P05.04
Enable threshold
P05.05
Multiplier
P05.01 = If set to OFF, the hour counters are disabled and the hour counter page is not shown.
P05.02 = If set to OFF, the partial hour counter is not incremented. If ON, time is incremented as long as DMG is powered. If set to ME S, the hour counter is
incremented depending on the condition defined by P05.03, P05.04 and P05.05.
P05.03 = Reference measurement for partial hour counter enabling.
P05.04 - P05.05 - Definition of the activation threshold for partial hour counter.
M06 - TREND GR PH
P06.01
Trend graph measurement
P06.02
utorange
P06.03
Full scale value
P06.04
Full scale multiplier
P06.01 - Selects the reading to be shown on trend graph page.
P06.02 - Choice between automatic range or fixed range defined by the user.
P06.03 - Full scale range value. The unit of measure is the one defined by the selected reading.
P06.04 - Full scale value multiplier.
M07 - COMMUNIC TION
P07.01
Serial node address
P07.02
Serial speed
P07.03
Data format
P07.04
Stop bits
P07.05
Protocol
Note: This menu is enabled only for DMG210.
P07.01 - Serial address (node number) for the communication protocol.
P07.02 - Serial communication speed.
P07.03 - Data format. Can be set to 7 bits for SCII protocol only.
P07.04 - Number of stop bits.
P07.05 - Communication protocol selection.
ENERGY METERS P GE
– The Energy meters page shows the following meters simultaneously:
• active energy imported and exported
• reactive energy imported and exported (inductive / capacitive)
• apparent energy.
– The main page shows the total meters. By pressing
– To clear energy meters, it is necessary to access the commands menu.
1 - Total / Partial indication
UdM
min
min
UdM
UdM
UdM
bps
key, the display moves to sub-page with partial meters (clearable by the user).
Default
Range
Shift
Fixed / Shift
15
1-60
15
1-60
Default
Range
ON
OFF-ON
OFF
OFF - ON - ME S
OFF
OFF - (measurement)
0
-9999 - +9999
x1
/100 - x10k
Default
Range
kW (tot)
VL-L (eq) VG
VG
kW (tot) VG
kvar (tot) VG
kV (tot) VG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
Default
Range
01
01-255
9600
1200
2400
4800
9600
19200
38400
8 bit - n
8 bit, no parity
8 bit, odd
8 bit, even
7 bit, odd
7 bit, even
1
1-2
Modbus RTU
Modbus RTU
Modbus SCII
5
G
B