Satco nuvo 67-138 Instrucciones De Instalación Y Seguridad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

LED EMERGENCY LIGHTS
Models: 67-138, 67-139
INSTALLATION AND SAFETY INSTRUCTIONS
IMPORTANT: Read before installing fixture. Retain for future reference.
WARNING: Risk of Fire or Electric Shock
• Disconnect power before installation or any
maintenance of the fixture.
• To avoid damage, falling, electric shock or fire, do not
modify the fixture or replace accessories.
• Only authorized, qualified personnel should install this
fixture and should follow the owner's manual.
• Do not dismantle the fixture.
• Do not touch the power supply when the fixture is operating.
• For use in environments where an accumulation of
non-conductive dust on the fixture may be expected.
• Damp rated. Do not use outdoors.
• Do not mount near gas or electric heaters.
• Do not let power cords touch hot surfaces.
• Use caution when servicing batteries. Avoid possible
shorting.
• Equipment should be mounted in locations and at heights
where it will not readily be subjected to tampering by
unauthorized personnel.
• The use of accessory equipment is not recommended
and may cause an unsafe condition.
• Do not use this equipment for other than intended use.
• Disconnect AC power and unplug battery before servicing.
• Battery in this unit may not be fully charged. After the
AC service is supplied to unit, let the battery charge up
for at least 24 hours before performing any tests.
IMPORTANT: This product must be installed in accordance
with the applicable installation code by a person familiar
with the construction and operation of the product and the
hazards involved.
MAXIMUM CEILING MOUNTING HEIGHT:
67-138, 67-139: 22ft (6.7m)
MAXIMUM WALL MOUNTING HEIGHT:
67-138, 67-139: 21ft (6.4m)
MAINTENANCE: Battery may need to recharge upon
initial power up. We recommend that the equipment be
tested regularly in accordance with local codes. Replace
the batteries as needed if discharge time does not achieve
90 minutes.
OPERATION: Press the test button, LED Heads will turn
on and the LED indicator will turn off. Release the test
button, LED indicator will turn on and the LED heads will
turn off.
© Copyright 2023 Satco Products, Inc. 2/23 v1.2
67-138
67-139: Remote Compatible
Use Flexible Conduit Only
WIRING DIAGRAM
TROUBLE SHOOTING GUIDE: If LED indicator
does not illuminate, check the following:
1. Check AC supply – verify that unit has 24 hours AC
supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours
then re-test.
1
Satco Products, Inc.
Brentwood, NY 11717
loading

Resumen de contenidos para Satco nuvo 67-138

  • Página 1 LED indicator will turn off. Release the test 3. Battery discharged. Permit unit to charge for 24 hours button, LED indicator will turn on and the LED heads will then re-test. turn off. Satco Products, Inc. © Copyright 2023 Satco Products, Inc. 2/23 v1.2 Brentwood, NY 11717...
  • Página 2 INSTALLATION: BACK POWER FEED Wall Mounting (Figure 2) Figure 1 1. Using flat screw driver pry off front cover from back plate (Figure 1). 2. Remove appropriate knockouts in back plate. 3. Feed wires through the hole. 4. Secure backplate to Junction Box. 5.
  • Página 3 ESPAÑOL LUCES LED DE EMERGENCIA INSTRUCCIONES DE INSTALACIÓN Y SEGURIDAD Modelos: 67-138, 67-139 IMPORTANTE: Lea esto antes de instalar el accesorio. Consérvelo para referencia futura. SEGURIDAD: Riesgo de incendio y descarga eléctrica • Desconecte la alimentación antes de la instalación o de cualquier mantenimiento a la luminaria. •...
  • Página 4 FRANCAIS LUMIÈRES D’URGENCE À DEL INSTRUCTIONS SUR L’INSTALLATION ET LA SÉCURITÉ Modelos: 67-138, 67-139 IMPORTANT: Lisez avant d’installer le luminaire. Conservez à titre de référence. SÉCURITÉ: Risque d’incendie ou de décharge électrique • Débranchez l’alimentation avant d’installer ou d’effectuer l’entretien du luminaire. •...

Este manual también es adecuado para:

Nuvo 67-139