Figura 44
Ejemplo de conexión para 4 cargas monofásicas, línea trifásica con neutro
Configuración Dip-Switches
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
Figura 45
Ejemplo de conexión para 4 cargas transformadores monofásicos, línea trifásica con neutro
Configuración Dip-Switches
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
Ver notas sobre utilización con cargas inductivas y transformadores
80404I_MHW_GFX4-IR_10-2019_ESP
Dip 4
Dip 5
OFF
OFF
Dip 4
Dip 5
OFF
ON
P
Id = ___
V cosj
V =
tensión de fase (línea / neutro)
P =
potencia de cada carga monofásica
Id =
corriente en la carga
si la carga resistiva cosj = 1
P
Id = _________
Is = _________
h . V . cosj
P = potencia de cada carga monofásica
V = tensión de fase (línea L1- lìnea L2/N)
Vload =tensión en el secundario (carga)
Id = corriente en el primario
Is = corriente en el secundario (carga)
h = rendimiento del transformador (tipo 0,9)
si la carga resistiva cosj = 1
P
Vload . cosj
33